VESDA Sensepoint XCL – Large Bore Installation Manual
VESDA
Modbus
Register
Address
Information
R/W
Type
Size
Description
Notes
40169 to
40170
Alarm Threshold 2
R
f 32
2
40171 to
40172
Target Calibration Gas
Concentration
R
f 32
2
40173
Gas Type
R
u16
1
l
0x00: Flammable
l
0x01: Toxic
l
0x02: O2
l
0x03: VOC
40174 to
40175
Voltage Output
R
f 32
2
Device's voltage output value corresponding gas conc.
(i.g, if gas conc. Is reached to full scale, voltage output
value is 1.0)
40176 to
40183
Device SN
R
string[16] 8
40184 to
40188
BLE FW Version
R
string[10] 5
BLE FW Version
40189 to
40200
Reserved
40201
Reset Alarms & Faults
W
u16
1
40202 to
40207
Reserved
40208 to
40213
Raw A/D Counts
R
u16[6]
6
43
www.xtralis.com