VESDA Sensepoint XCL – Large Bore Installation Manual
VESDA
Modbus
Register
Address
Information
R/W
Type
Size
Description
Notes
40114
Relay Fitted
R
u16
1
0x00: Relay not fitted, 0x01: Relay fitted
40115
BLE Fitted
R
u16
1
0x00: BLE not fitted, 0x01: BLE fitted
40116
Reserved
R
u16
1
40117
Temperature (°C)
R
s16
1
Transmitter temperature
40118 to
40122
Reserved
40123 to
40131
Date and Time
R
string[18] 9
Format is “mm/dd/yy hh:mm:ss”
40132
Sensor Technology
R
u8
1
Sensor type only, not a specific gas type
l
0x00 :ECC
l
0x01: FL CAT
l
0x02: IR
l
0x03: PID (not in use)
l
0x04: MOS (not in use)
40133 to
40134
Gas reading (by status)
R
f32
2
Gas reading value calculated by device status (i.g
negative value in fault status )
1. If device is in Inhibit state, return value is base
concentrate of sensor data (In case of ECC,
Noramlly 0)
2. If device is in fault state, return value is :
3. return = f32_gas_full_scale / 16 * (fault current
value of configuration - 4.0);
4. If device is in warning state, return value is : return
= f32_gas_full_scale / 16 * (warning current value
of configuration - 4.0);
same as '30035 to 30036'
40135 to
40136
Reserved
40137 to
40138
Microcontroller
Operating Voltage
R
f32
2
Operating voltage of MCU
40139 to
40140
Microcontroller
Reference Voltage
R
f32
2
Reference voltage
40141
BLE Connection Status
R
u8
1
Connection status with BLE module
0x00: Not connected, 0x01: Connected
40142 to
40145
Reserved
41
www.xtralis.com