A
Appendices
A.1
Detector Parameters
Gas
Detector Type
User Selectable
Range
Default
Range
User Selectable
Cal Gas Range
Default Cal
Point
Response Time T
90
(s) – Standalone
Resolution
Accuracy (greater of
ppm or % of applied gas)
Carbon Monoxide (ppm)
XCL-LB-CO..
50 to 1000ppm
300ppm
20 to 70% of
selected full scale
range
100ppm
<30
1ppm
< ±2ppm or ±10%
Flammable CAT (% LEL)
XCL-LB-CH4..
20 to 100% LEL 100% LEL
50% LEL
<30
1% LEL
< ±3%LEL or ±10%
Hydrogen (ppm)
XCL-LB-H2..
1000ppm (Fixed) 1000ppm
500ppm
<120
1ppm
< ±15ppm or ±20%
Carbon Dioxide (% v/v)
XCL-LB-CO2VV..
1.0 to 5.0% v/v
5.0% v/v
2.5% v/v
<30
0.1% v/v
< ±0.2% v/v or ±20%
Carbon Dioxide (ppm)
XCL-LB-CO2PP..
1000 to 5000ppm 5000ppm
2500ppm
<30
10ppm
< ±30ppm or ±20%
Hydrogen Sulphide (ppm)
XCL-LB-H2S..
10 to 50ppm
50ppm
25ppm
<30
0.1ppm
< ±0.3ppm or ±10%
Nitrogen Dioxide (ppm)
XCL-LB-NO2..
5 to 50ppm
20ppm
5ppm
<120
0.1ppm
< ±0.2ppm or ±20%
Ammonia (ppm)
XCL-LB-NH3..
50 to 200ppm
100ppm
50ppm
<200
1ppm
< ±4ppm ±20%
Oxygen (% v/v)
XCL-LB-O2..
25.0% v/v (Fixed) 25.0% v/v
20.9% v/v
<30
0.1% v/v
< ±0.5 % v/v
Gas
Operating
Temperature
Default Alarm Points & Types
LAL
1
LDL
2
Min
Max
A1
Default A1
Type
A1 Options
A2
Default A2 Type
A2 Options
Carbon Monoxide(ppm)
-20°C
50°C
30ppm
Rising
Rising/Disabled
100ppm
Rising
Rising/Disabled
15ppm
10ppm
Flammable CAT (% LEL)
20% LEL
50% LEL
10% LEL
6% LEL
Hydrogen (ppm)
200ppm
400ppm
100ppm
30ppm
Carbon Dioxide (% v/v)
0.4% v/v
0.8% v/v
0.2% v/v
0.1% v/v
Carbon Dioxide (ppm)
1500ppm
3000ppm
500ppm
300ppm
Hydrogen Sulphide (ppm)
10ppm
20ppm
1ppm
0.8ppm
Nitrogen Dioxide (ppm)
0.7ppm
2ppm
0.6ppm
0.3ppm
Ammonia (ppm)
20ppm
50ppm
20ppm
6ppm
Oxygen (% v/v)
23.5% v/v
19.5% v/v
Falling
Falling/Disabled
5.0% v/v
3% v/v
1
LAL Lower Alarm Level (lowest alarm level that user can set)
2
LDL Lower Detection Limit (lowest detectable level that device can display)
VESDA
VESDA Sensepoint XCL – Large Bore Installation Manual
www.xtralis.com
32