The VFD controller is adjusted at the factory to the values displayed in the chart below.
All XLT Hoods are functionally tested at the factory. Operation is verified, and adjust-
ments are made to ensure proper operation. However, field conditions are sometimes different
than factory conditions.
It is necessary to have an authorized service technician verify operation
and make field adjustments if needed.
The following items must be checked and verified to meet the specifications and require-
ments stated in this manual prior to the hood being commissioned:
Correct fan rotation
Balanced make-up air
The Hood Initial Start-Up Checklist, found at the end of this manual, must be completed
(both sides) at time of installation, signed by the Customer and returned to XLT and the Author-
ized Distributor to initiate Warranty Policy.
If the Start-Up Checklist is not filled out completely
and returned to XLT, the Warranty will not be honored.
Variable Frequency Drive Adjustments
HOOD INITIAL START-UP
If you require either more or less air flow, follow these steps:
(Reference Hood
User Interface image on next page)
1. Press & hold the LIGHTS and XLT LOGO buttons to enter into factory tech mode.
2. Use the Up/Down arrows to reach manual air balance.
3. Press and hold ENTER button for 3 seconds. Entire row will flash.
4. Scroll to desired oven setting. Press ENTER.
5. +/- should flash and it /- change up to 10 Hz.
6. Press ENTER to save changes.
7. Press ON to test air balance.
Top Middle Bottom
Single
X
20 Hz
25 Hz
30 Hz
X
20 Hz
25 Hz
30 Hz
X
35 Hz
40 Hz
45 Hz
X
X
35 Hz
40 Hz
45 Hz
X
20 Hz
25 Hz
30 Hz
X
30 Hz
35 Hz
40 Hz
X
40 Hz
45 Hz
50 Hz
X
X
30 Hz
35 Hz
40 Hz
X
X
40 Hz
45 Hz
50 Hz
X
X
40 Hz
45 Hz
50 Hz
X
X
X
45 Hz
50 Hz
55 Hz
VFD Controller Settings
Ovens On
1832 & 2440
3240, 3255 & 3270 3855 & 3870
Fire Suppression
60 Hz DO NOT CHANGE
Triple
Double