HOOD ELECTRICAL REQUIREMENTS
Inputs into Electrical
The XLT Hood system provides:
Up to three (3) switching outputs for HVAC damper and/or dedicated unit.
One (1) 230 VAC, 10 Amp, variable frequency, three phase power output for the ventilation
exhaust fan.
Up to three (3) receptacles for ovens.
One (1) 24 VDC fire alarm signal.
Relocation cord will physically connect into oven.
Outputs from Electrical
Receptacles
Outlets
Do not connect to 3 Phase power. 1 Phase Only.
CAUTION
# of Circuits
Rating
Purpose
1
208/240 VAC, 1 Phase, 60 Hz, 6 Amp
VFD Controller
up to 3
120 VAC, 1 Phase, 60 Hz, 20 Amp
Ovens
XLT Hood Electric Utility Specifications
Standard