22
DIAGNOSTIC LEDS MEANING
FIRST CONFIGURATION
If the device is not configured initially, the three LEDs will be simultaneously blinking, to indicate that the
device is waiting for receiving the configuration SMS or the first web configuration.
This initial configuration can also be obtained by performing a device factory reset.
NORMAL OPERATION
During normal working operation, LEDs must have the following status:
LED STATUS
>
green blinking
LED NET
>
red fixed on
LED FIELD
>
off with short blinks during Modbus polling activity
MALFUNCTION INDICATIONS
Led STATUS solid orange
If the STATUS led is solid orange, an hardware error has occurred. Please contact Technical Support.
Led STATUS blinking orange/red alternately
In this case, the device is polling the slave devices via Modbus protocol, but some reading errors persist.
Led FIELD solid red
If the FIELD led is solid red, the Rilheva device is not communicating correctly with the Modbus devices.
Led NET blinking fast (about 10 flashes/sec)
This indication tells that a severe hardware error is present. Please contact Technical Support.
Led NET blinking slow (about 2 flashes/sec)
In this case, there can be some problem with the SIM card. Please check that SIM card is active, properly
installed into the slot and with PIN lock feature disabled.