![Xeo4 RILHEVA II User Manual Download Page 26](http://html1.mh-extra.com/html/xeo4/rilheva-ii/rilheva-ii_user-manual_3278561026.webp)
26
Data formats
Rilheva II supports the following Modbus datatypes:
Data format
Modbus format
Data for
registers
Type
Sign
Range
Bit size
F1
Single register LSB
part
2
Integer
unsigned
0-255
8
F2
Singe register MSB
part
2
Integer
unsigned
0-255
8
F3
Single register
1
Integer
unsigned
0-65535
16
F4
Single register
1
Integer
signed
-32768 +32767
16
F5
Couple of registers
HI-LO
1
Integer
unsigned
0- 4294967295
32
F6
Couple of registers
HI-LO
1
Integer
signed
-2147483648
+2147483647
32
F7
Couple of registers
1
Floating
signed
See IEEE 754
32
F8
Single bitwise
register
16
Bit
-
0-1
16
F9
Couple of registers
LO-HI
1
Integer
unsigned
0- 4294967295
32
F10
Couple of registers
LO-HI
1
Integer
signed
-2147483648
+2147483647
32
Summary of Contents for RILHEVA II
Page 1: ...1 RILHEVA II USERMANUAL V 1 5...
Page 6: ...6 SYSTEMARCHITECTURE...
Page 8: ...8 DEVICEINSTALLATION Some installation examples follow...
Page 9: ...9...
Page 18: ...18...
Page 33: ...33 ITEMSIZES...