Specifications
A–2
975-0384-01-02
This manual for use by qualified personnel only
Electrical Specifications
Table A-1
Xantrex XW Power System Electrical Specifications
Xantrex
XW6048 230 50
Xantrex
XW4548 230 50
Xantrex
XW4024 230 50
Continuous Output Power
6,000 W
4,500 W
4,000 W
Surge Rating
12,000 W (15 s)
9,000 W (20 s)
8,000 W (20 s)
Surge Current
53 A
rms
(15 s)
40 A
rms
(20 s)
35 A
rms
(20 s)
Peak Efficiency
95.4%
95.6 %
94.0%
Full Load Efficiency
92%
93.0 %
89%
Waveform
True Sine Wave
Idle Consumption—invert mode, no load
28 W
26 W
24 W
Idle Consumption—search mode
< 7 W
AC Output Voltage
230 Vac ±3%
AC Input Voltage Range (Bypass/Charge Mode) 156–280 Vac
AC Input Breaker
60 A
AC Input Frequency Range (Bypass/Charge
Mode)
45–55 Hz (default)
40–68 Hz (allowable)
AC Output Continuous Current
26.1 A
19.6 A
17.4 A
AC Output Frequency
50.0 ±0.1 Hz
Total Harmonic Distortion
< 5% at rated power
Automatic Transfer Relay
56 A
Auxiliary Relay Output
0–12 Vdc, maximum 250 mA DC
DC Input Voltage (Nominal)
50.4 Vdc
50.4 Vdc
25.2 Vdc
DC Input Voltage Range
40–64 Vdc
40–64 Vdc
20–32 Vdc
DC Current at Nominal Power
131 A
96 A
178 A
Continuous Charge Rate at Nominal Voltage
100 A
85 A
150 A
Power Factor Corrected Charging
PF (0.98)