
Pre-Installation
975-0384-01-02
2–3
This manual for use by qualified personnel only
Clearance Requirements
Provide a minimum clearance of 150 mm (300 mm is preferred) around the top
and 150 mm at the bottom of the inverter for ventilation. The front of the inverter
must have at least one meter of clearance. Make sure that the vents are not
obstructed with foreign objects and that the minimum clearances are met.
Mounting
The Xantrex XW Power System is designed to be mounted on a vertical surface.
The supporting surface must be strong enough to support a minimum of 60 kg
for a single inverter/charger. To facilitate installation, a wall mounting plate (Part
Number 210-0462-01-01) is provided for each Xantrex XW Inverter/Charger. The
mounting plate and hardware on the Xantrex XW Inverter/Charger are designed
to meet standards for structural and seismic stability.
Figure 2-1
Clearance Requirements
150 mm minimum
clearance
150 mm minimum
clearance
Summary of Contents for XW4024 230 50
Page 2: ...YOUR SCHNEIDER ELECTRIC DISTRIBUTOR SOLIGENT 800 967 6917 www soligent net...
Page 3: ...Xantrex XW Hybrid Inverter Charger Installation Guide www schneider electric com...
Page 8: ...vi...
Page 18: ...1 8...
Page 56: ...2 38...
Page 66: ...IX 2...
Page 67: ......