Step 4: Wiring the Inverter
975-0384-01-02
2–27
This manual for use by qualified personnel only
AUX-RPO: User Remote Power Off (RPO)
Connecting JU-2 (AUX-RPO) and JU-3 (AUX-COM) terminals together through
an external switch (normal open contact) provides the system shut off function if
the switch is closed.
The external switch, if pressed, overrides the control provided from the front
panel.
If the external switch is cleared (not pressed), the system can be enabled back
from the front panel.
Select an external switch with normal open contact. Consult your system
designer or qualified technician for specific installation instructions.
User Line Wiring
Use twisted pairs of #24 AWG to #12 AWG (0.5 mm
2
to 2.5 mm
2
) for connections.
Carefully route the wires away from high power load cables to minimize noise
effects on signal integrity.
AUX Port Terminal Assignments
Table 2-7
User Connector Terminals and Functions
Pin
Reference
Name
Function
JU-1
AUX+12V
+12 V User
Voltage Supply
+12 VDC Voltage source: 250 mA
maximum
JU-2
AUX-RPO
Remote Power
Off
Remote Power Off Logic Level:
Active Low. Activating this signal
shuts down system operation.
JU-3
AUX-COM
Common Ground
Reference
Return Common Ground
Reference for 12V, Remote Power
Off signals.
JU-4
Not
Operational
Not Operational
Not Operational
JU-5
Not
Operational
Not Operational
Not Operational