Planning
2–4
975-0289-01-01
Dimensions
Figure 2-1
Dimensions (not to scale)
14.25”
(35.56 cm)
14”
(35.56 cm)
13.875”
(35.24 cm)
20.5”
(52.7 cm)
16”
(40.64 cm)
8”
(20.32 cm)
IMPORTANT:
Allow 8" minimum clearance
around the back of this unit for
ventilation. (12" preferable).
Be sure to leave adequate
space for access if the unit is to
be hardwired. 12" may not be
adequate.
IMPORTANT:
The Powerhub should be
mounted on concrete floors or
on floors designed to support
a minimum load of
100 pounds per square foot.
Front
22”
(55.88 cm)
Recommended Minimum Required Floor Space =
22" (55.88 cm) x 33" (84 cm)
Back
29”
(73.7 cm)
20.5”
(52.7 cm)
12" Clearance
8" Clearance
Equipment
Footprint
33” (84 cm)