Installation
3–12
975-0289-01-01
Removing the Factory-installed AC Cord and Knockouts
DC Input (80 A DC Input/100 A fused)
Manufacturer’s recommendation.
20.3 Nm (180 in-lbs)
DC Ground
Manufacturer’s recommendation.
20.3 Nm (180 in-lbs)
System Ground
#3 AWG
Figure 3-10
Removing the AC Cord
Table 3-1
Recommended Wire Gauges for Input and Output Terminals
Terminal
Acceptable Wire Gauge
Torque to.....
1. Locate the AC wiring from the
cord and loosen the screws on
the Ground, Line 1 (L1), and
Neutral terminals.
2. Remove the 3 #6-32
Phillips screws on the AC
cord access plate and
remove the plate along
with the cord.
Proceed to Figure 3-11.