Installation
3–18
975-0289-01-01
DC Wiring (Renewable Energy Wind, Maximum 1000 W)
Important:
Renewable energy input may require additional hardware to be
code-compliant. There may also be additional grounding requirements. Be sure
to consult your local electric authority for additional requirements.
Figure 3-16
Connecting the DC Input (Renewable Energy Wind)
Example only. Actual installation may vary.
Torque Positive, Negative, and
Ground terminals to
20.3 nm (180 in-lbs)
IMPORTANT:
The wind generator needs its
own charge controller to
properly charge batteries.
Consult wind turbine
manufacturer for specific wiring
instructions.
Torque Neutral and Line terminals
to 1.3 nm (11.5 in-lbs)
Torque Ground terminal
to 1.8 nm (16.0 in-lbs)
975-0289-01-01(PowerHub_1800_IG).book Page 18 Thursday, June 4, 2015 9:49 AM