3.5.1.6 Option Island Grid Function
If the product has the island grid function, an external voltage (+24 V
DC
) must be
applied on the terminals (-X17.1-2) so that the product can also operate parallel to the
grid. By disconnecting the external voltage via an external disconnecting device, the
product can establish an island grid.
The terminals (-X17.1-2) are implemented as a potential-free feedback contact. A
signal on these feedback contacts manages the switching in and out of the island grid
mode.
Figure 16: Wiring diagram extract terminal strip (-X17)
Procedure:
1.
Locate
terminal strip (-X17) (Figure 5).
2.
Connect
power supply (+24 V
DC
o
DC (+)
to terminal (-X17.1)
o
DC (-)
to terminal (-X17.2)