11.2 Technical Data
11.2.1 Electrical Data
Table 10: Electrical data
BATx0100-ES-1-400-1
Remarks
AC SIDE
Max. AC apparent power
120 kVA (2h)
At nominal grid
voltage
Nominal AC power
100 kW
At (cos
(φ)) = 1.0
Nominal grid voltage (U
AC,nom
)
400 V
Other values on
request
Nominal grid voltage range
± 10 % of U
AC,nom
System type
TN-Grid,
3~ (phase to phase) +
neutral, 50 Hz
Max. AC current
173 A
Max. short circuit level
36 kA
Power factor
(cos φ)
> 0.98
At > 20 % of nominal
AC power
AC current distortion (THD)
< 3 %
DC SIDE
Nominal DC voltage
750 V
DC voltage range
450 … 890 V
DC current range
+/- 250 A
Max. short circuit level
40 kA
Current THD
< 3 %
Independent DC sources
1
GENERAL
Control strategy
CC-CV,
Power controlled,
ISLAND GRID
Efficiency
(93.9|96.9|97.1|97.0|96.7) %
At
(10|30|50|75|100) %
power
Lost in standby at night
< 30 W
Max. auxiliary power
< 250 W
Excluding optional
heating
MEASURING ACCURACY
AC-voltage
2% of nominal grid voltage
Grid frequency
+/- 80 mHz
Average value of 5
grid periods