Inspection and maintenance
Greenstar 2000 – 6 721 820 552 (2021/02)
60
9.3
Component access
Removing the front casing
The front casing is secured with two screws which are critical to maintain
the case seal and to prevent unauthorised removal (electrical safety).
▶ Always secure the casing with these screws.
▶ Loosen the two screws [1] and pull the bottom of the casing forward.
▶ Lift off the casing.
Fig. 71 Removing the front casing
9.4
Fan pressure test
NOTICE
Fan pressure test
▶ The appliance must be running at maximum output in chimney sweep
mode for the fan pressure test, (
Setting the appliance to
maximum).
This test is to determine if the heat exchanger requires cleaning or
additional actions.
Fan pressure test reading.
▶ The pressure reading will be in negative values.
9.4.1
Checking heat exchanger assembly
▶ Remove the front casing.
▶ Remove the cap from the test nipple, and connect a pressure gauge.
Fig. 72 Test nipple at the mixing device
Appliance fan pressure test values
Natural Gas and LPG appliances
Table 32 Natural Gas and LPG values
If the manometer reading is within tolerance
, in the white area of the
table values.
▶ The heat exchanger/exhaust path/siphon does not require attention.
If the manometer reading is out of tolerance
, in the shaded area of the
table values then carry out the following checks.
▶ Check that the siphon is not restricted or blocked.
▶ Check the exhaust paths for restrictions.
▶ Clean the heat exchanger with a suitable cleaning tool, refer to
cleaning section.
▶ Re-check the fan pressure readings.
If the appliance, after completing the above checks, fails the fan
pressure test then contact Worcester, Bosch Group for advice.
▶ Switch the appliance off after completing pressure check.
▶ Disconnect the digital manometer and replace the test point cover.
9.5
Check working gas inlet pressure
NOTICE
Gas inlet pressure
▶ Do not continue with the other checks if the correct gas inlet pressure
can not be achieved at maximum output.
▶ Check the gas supply working pressures in the system conform to the
readings shown in the table shown in chapter 6.6 "Checking gas inlet
pressure".
1
0010029675-001
Appliance
output
Cleaning required
No cleaning required
Value
30kW
0 mbar
-4.7 mbar -4.8 mbar
-12 mbar
25kW
0 mbar
-3.2 mbar -3.3 mbar
-12 mbar
0010036064-001