Manual 04121
ProAct I/II
Woodward
63
ProAct™ Control Specifications
Operating Temperature
–40 to +85 °C (–40 to +185 °F)
Storage Temperature
–55 to +100 °C (–67 to +212 °F)
Vibration
Sine Sweep, 6 hrs/axis, 24-2000 Hz
0.5 Oct./min input level 2.5 Gs
Shock
US MIL-STD-810C, Method 516.2, Procedure III
Transit Shock
US MIL-STD-810C, Method 516.2, Procedure IV
EMI/RFI:
Conducted
Susceptibility
Frequency (Hz)
Amplitude (Vrms)
Power Leads—
30–1000
3.0
1000–10
000
3.5
10 000–8 000 000
1.5
8 000 000–1000 000 000
1.0
All other leads—
30
000–500
000
0.5
500 000–1 000 000
1.0
Radiated Susceptibility:
Control will not fail in an unsafe manner up to 55
V/m, 15 kHz to 1000 MHz
Humidity:
95% ±5% at 60 °C for 6 hrs
50% ±5% at -40 °C for 2 hrs