Figure 4-10. Idle Droop
19. Speed Switch C OFF sets the rpm that will turn off Speed Switch C.
The speed switch changes state at the selected speed position. Each switch
allows 500 mA to sink to the negative of the power supply when closed.
Figure 4-11. Speed Switch Settings
Menu 4—Limiter Settings
Fuel limiters limit the actuator output from the control. Descriptions of each menu
item follow.
1.
Maximum Fuel Limit sets the maximum percent actuator output when rated
speed is selected. If the actuator linkage is correctly set so the actuator is
providing the maximum position stop, 3° in advance of the butterfly valve
maximum position, this item may be set at 100%. If the actuator must reach
maximum before it reaches its maximum stop, the entry must be below
100%.