Menu Summary
Initial Prestart Settings
These tables are provided for the convenience of the ProAct™ user. Each
number should be recorded as it is programmed with the Hand Held
Programmer. Any changes should be noted so the adjustment can be referenced
from its original setting.
Please refer to application note 51317, ProAct Digital Speed Control
System with Start-up Fuel Limiting, if this is a fuel-limiting version.
Menus 3 and 4 have additional settings.
Menu 1—Dynamics Settings
Gas
Diesel
Engine
Engine
Default
Prestart
Prestart
Menu
Item
Setting Setting Setting Actual
Setting
Gain
A
0.25 0.025 0.050 ___________
Gain A break point
0%
100%
100%
___________
Gain
B
0.25 0.025 0.050 ___________
Gain B break point
30%
100%
100%
___________
Gain
C
0.25 0.025 0.050 ___________
Gain C break point
60%
100%
100%
___________
Gain
D
0.25 0.025 0.050 ___________
Gain D break point
100%
100%
100%
___________
Stability
0.25 sec.
1.0 sec.
1.0 sec.
___________
Compensation
0.10 sec.
0.15 sec.
0.15 sec.
___________
Gain
Ratio
1.00
1 1 ___________
Gain Window
60 rpm
60 rpm
60 rpm
___________
Menu 2—Alternate Dynamics Settings
Gas
Diesel
Engine
Engine
Default
Prestart
Prestart
Menu
Item
Setting Setting Setting Actual
Setting
Alt Gain A
0.10
0.025
0.050
___________
Gain A break point
0%
100%
100%
___________
Alt Gain B
0.10
0.025
0.050
___________
Gain B break point
30%
100%
100%
___________
Alt Gain C
0.10
0.025
0.050
___________
Gain C break point
60%
100%
100%
___________
Alt Gain D
0.10
0.025
0.050
___________
Gain D break point
100%
100%
100%
___________
Alt Stability
1.0 sec.
1.0 sec. 1.0
sec. ___________
Compensation
0.20 sec.
0.15 sec.
0.15 sec.
___________
Alt
Gain
Ratio
1 1 1 ___________
Alt Gain Window
60 rpm
60 rpm
60 rpm
___________
Summary of Contents for ProAct I
Page 10: ...ProAct I II Manual 04121 8 Woodward Figure 1 3 Example of ProAct II Actuator...
Page 11: ...Manual 04121 ProAct I II Woodward 9 Figure 1 4 Outline Drawing of ProAct I or II Actuator...
Page 12: ...ProAct I II Manual 04121 10 Woodward Figure 1 5 ProAct Wiring Diagram...
Page 13: ...Manual 04121 ProAct I II Woodward 11 Figure 1 6 Outline Drawing of ProAct Control Box...
Page 39: ...Manual 04121 ProAct I II Woodward 37 Figure 4 2 Typical Transient Response Curves...