WirelessHART Fieldgate SWG70
10 Engineering
Hauser
65
Input Status parameters
Parameter
Meaning
Example
Default
Table
Register
Defines the start register for the Digital I/O device values
– For Input Status the first value is normally 1
– The initial value can be overwritten only after a device has been
selected in the Long Tag drop-down menu
– Subsequent start registers are automatically generated
1
1
End Register
End register for Digital I/O device values (generated automatically) 8
65536
Long Tag
Click to open a drop-down list of connected network devices
–
–
IO-Card
Identifier of fieldgate card used by the device
–
–
Channel
Identifier of card channel used by the device
–
–
Value
Click to open a drop-down list of values for the selected device
– Least Significant Byte: maps bits 0 - 7 of a UINT16 to one register
each
– Most Significant Byte: maps bits 8 - 15 of a UINT16 to one
register each
–
–
Value field
Enter an appropriate value into the field which opens when a value
is selected
– 0: the 1st discrete value of a device is mapped
...
255: the 256th discrete value of a device is mapped
0
0
Delete button
Depending upon position, deletes the table or the table line
–
–
Generate
Start Register
Defines the start register for the first Digital I/O device
– For Input Status this is normally 1
1
1
Generation Order
Order in which the devices are mapped to the Modbus registers.
• Index: According to the index number, see Instrument List,
Chapter 10.1, for example
• Alphabetical: In alphabetical order according to the Long Tag
• Alphabetical (sub-device): In alphabetical order according to the
Long Tag of the sub-device.
• IO card & channel: According to the IO card & channel number
of the wireless device.
• IO card & channel (sub-device): According to the IO card &
channel number of the sub-device.
–
–
Value
Click to open a drop-down list of values for the selected device
– Least Significant Byte: maps bits 0 - 7 of a UINT16 to one register
each
– Most Significant Byte: maps bits 8 - 15 of a UINT16 to one
register each
–
–
Value field
Enter an appropriate value into the field which opens when a value
is selected
– 0: the 1st discrete value of a device is mapped
...
255: the 256th discrete value of a device is mapped
0
0
Delete button
Depending upon position, deletes the table or the table line
–
–
Generate
Writes mapping table to table in Table tab
–
–
Delete all mappings
• Checked: Overwrites any table already in Table tab
• Unchecked: Adds any new devices found to existing table
–
–
Controls
Import
Imports a mapping table in CSV format
–
–
Export
Exports the current mapping table in CSV format
–
–
Refresh
Loads the mapping table currently stored in Fieldgate SWG70
–
–
Apply
Stores the current mapping table to Fieldgate SWG70
–
–
Summary of Contents for Fieldgate SWG70
Page 2: ......
Page 119: ...WirelessHART Fieldgate SWG70 D Appendix ANATEL Approval Endress Hauser 117 For your notes ...
Page 120: ...D Appendix ANATEL Approval WirelessHART Fieldgate SWG70 118 Endress Hauser For your notes ...
Page 121: ...WirelessHART Fieldgate SWG70 D Appendix ANATEL Approval Endress Hauser 119 For your notes ...
Page 123: ......
Page 124: ...www endress com worldwide ...