4094-00

60708-162

11

3.  As the unit starts release the Start Switch and it will return to 

the run position.  You must continue to depress the Safety Latch 

Relay button until the Check Engine light goes out.  When this 

light goes out, it indicates that the engine has built sufficient oil 

pressure to operate properly and the high coolant temperature 

has not been exceeded.  

   *************

*****  WARNING  *****

    ************* 

EQUIPMENT DAMAGE

 - DO NOT DEPRESS THE SAFETY 

LATCHING RELAY BUTTON FOR OVER 10 SECONDS.  IF THE 

LIGHT HAS NOT GONE OUT IN 10 SECONDS IT INDICATES 

THAT EITHER THE ENGINE HAS NOT BUILT OIL PRESSURE 

OR THE COOLANT TEMPERATURE HAS EXCEEDED THE 

ALLOWABLE MAXIMUM.

4. After the engine is up an running the circuit breaker can be 

closed to power your loads.  During periods of very cold operation 

it is best to let the engine warm up for a few seconds before 

applying the load.

5.  When stopping the unit it is best to turn off all the loads before 

turning the Start Switch to the off position.  This prevents your 

loads from getting low voltage while still running during unit 

shutdown.

If for some reason during operation the oil pressure should drop 

below the allowable oil pressure or the water temperature should 

exceed allowable level the Safety Latching Relay button will pop-

out and the unit will shutdown.  You will also get a check engine 

light at this time.  

If you find the unit stopped with the relay button popped-out, it 

could have been caused by either low oil pressure or high water 

temperature.

DSE 3110 ELECTRONIC 

START CONTROL 

A. Deep Sea 3110 Engine Control - 

See controller explanation 

on the following page.

B. 2 AMP FUSE -

 This fuse is in the AC input line from the 

generator.  This feed that provides the AC voltage reading on 

the display.  If this fuse is blown the DSE 3110 will not display a 

voltage or frequency reading and will shutdown on low voltage or 

frequency. (Replacement fuse ATO-ATC 2A-250 Volt)

C. 2 AMP FUSE -

 This fuse supplies the 12 volt DC to power the 

DSE 3110 controller circuity on the boards.  If this fuse is blown 

the DSE 3110 will not function at all. (Replacement fuse ATO-ATC 

2A-250 Volt)

D. 10 AMP FUSE -

 This fuse supplies the 12 volt DC to power 

the two pilot relays in the control panel (one relay operates the 

fuel system and the other operates the starting system).  If this 

fuse is blown the DSE 3110 will show the unit has gone in a start 

mode but nothing will happen out on the engine generator set. 

(Replacement fuse ATO-ATC 10A-250 Volt).

E.  START SYSTEM PILOT RELAY- 

This is the pilot relay drives 

the starter solenoid on the engine starter.  When the DSE 3110 

calls for the unit to start, this relay is closes sending a 12V 

positive signal (lead #22) to the control terminal on the start 

solenoid mounted on top the starter on the engine.  This relay will 

open when the DSE 3110 senses voltage and frequency on AC 

feedback circuit from the generator disconnecting the starter.

F.  FUEL SYSTEM PILOT RELAY- 

This is the pilot relay for the 

both the fuel solenoid and the 12V field signal for the alternator 

on the engine starter.  When the DSE 3110 calls for the unit to 

run this relay closes and sends a 12V positive (lead #21) to both 

the fuel solenoid and the field circuit on the engine alternator.  

This relay will stay closed as long as the DSE 3110 is in the run 

position or until a safety shutdown is activated, at which time the 

relay will open.  When the relay opens all power to lead #21 is 

disconnected and the engine will shut down.  Also if the engine 

has shutdown one of the safety shutdown a fault code will be 

displayed.  These codes will be discussed later.

Summary of Contents for DE20I4

Page 1: ...INSTALLATION AND OPERATIONS MANUAL with STAMFORD GENERATORS MODELS DE20I4 DE30I4 DE45F4 DE65F4 DE90F4 MANUAL KEY START AND DSE3110 ELECTRIC START ELECTRIC START DIESEL GENERATORS...

Page 2: ...NUMBER________________________ M Spec ______________________________ PURCHASE DATE_______________________ DEALER_______________________________ TABLE OF CONTENTS INTRODUCTION i GUIDE TO PRODUCT SAFET...

Page 3: ...into the earth 2 FIRE HAZARD Diesel fuel presents a hazard of possible explosion and or fire a Do not smoke or use open flame near the generator set b Keep a fire extinguisher nearby and know its prop...

Page 4: ...000 Volts 120 240 120 208 120 240 277 480 Phase single three three three PF 1 0 80 80 80 AMPs 125 104 90 45 Hertz 60 60 60 60 Engine Model Isuzu 4LE TurboCharged Starting System 12 Volt Manual Start M...

Page 5: ...omponents also have their own individual identity plates providing additional information to document build data for warranty and replacement parts Be sure to have the main WINPOWER unit data plate in...

Page 6: ...to the entire standby generator line It is the responsibility of the installing party to follow the lifting equipment s operators manual to prevent injury to personnel and damage to the generator Smal...

Page 7: ...tor discharge These fresh air inlets should also be 1 1 2 to 2 times large than the radiator face The extra air inlet area is required to minimize restriction and to provide combustion air for the eng...

Page 8: ...ine manufacturer s maintenance instructions INSTALLING THE BATTERY CAUTION In the following battery installation procedure check to be sure the engine control is in the stop position This should be yo...

Page 9: ...are tight and coat the terminals and cable ends with dialectic grease WARNING The electrolyte is a diluted sulfuric acid that is harmful to the skin and eyes It is electrically conductive and corrosi...

Page 10: ...60708 162 4094 00 CONTROL BOX AC WIRING...

Page 11: ...77 480 3 45 14 1 0 AWG 80 in lbs kW Voltage PH Amp Wire Capability Lug Torque 45 120 240 1 175 4 AWG 300 MCM 250 in lbs 45 120 208 3 150 4 AWG 300 MCM 250 in lbs 45 120 240 3 150 4 AWG 300 MCM 250 in...

Page 12: ...SE This fuse protect all the DC wiring in the engine control panel and on the engine If this fuse if blown nothing will work on the engine E SAFETY LATCHING RELAY This safety latching relay provides t...

Page 13: ...s the AC voltage reading on the display If this fuse is blown the DSE 3110 will not display a voltage or frequency reading and will shutdown on low voltage or frequency Replacement fuse ATO ATC 2A 250...

Page 14: ...on places the module into its Automatic mode This mode allows the module to control the function of the generator automatically The module will monitor the remote start input and once a start request...

Page 15: ...high water temperature 5 After the engine is up an running the circuit breaker can be closed to power your loads During periods of very cold operation it is best to let the engine warm up for a few s...

Page 16: ...ailed below Press 4 to select the next parameter or 3 to select the previous parameter within the current page When viewing the parameter to be changed press the 1 button The value begins to flash Pre...

Page 17: ...high engine temperature pre alarm setting level after the Safety On timer has expired UNDERSPEED The engine speed has fallen below the underspeed pre alarm setting OVERSPEED The engine speed has rise...

Page 18: ...fective fuel pump 7 Defective fuel solenoid 8 Defective engine harness 9 Improper battery voltage to fuel pump or fuel solenoid ENGINE STARTS AND THEN STOPS AND ALARM LIGHT COMES ON 1 Engine oil press...

Page 19: ...4094 00 60708 162 17 START CONTROL PANEL ENGINE WIRING HARNESS DE20 DE30 KEY START SCHMATIC...

Page 20: ...60708 162 4094 00 18 START CONTROL PANEL ENGINE WIRING HARNESS DE45 DE65 KEY START SCHMATIC...

Page 21: ...4094 00 60708 162 19 DE20 DE30 3110 ELECTRIC START PANEL LEFT BLANK INTENTIONALLY AT THIS TIME...

Page 22: ...60708 162 4094 00 20 86 85 30 87a 87 86 85 30 87a 87 DE45 DE65 DE90 3110 ELECTRIC START PANEL...

Page 23: ...4094 00 60708 162 21 THREE PHASE AC WIRING HIGH AND LOW WYE...

Page 24: ...60708 162 4094 00 22 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING...

Page 25: ...nual Start Oil Filter 2 required 2992544 Pre Fuel filter Water Sep 2992662 Water Sensor 4254020 Fuel Filter Elements 2994048 Air Filter Element 8025818 Alternator Belt 500341810 Alternator 500315943 S...

Page 26: ...r additional oil information Oil Capacity 13 5 Quarts Cooling System 50 50 Mix MODEL DE90I4 3 DE90I4 4 DE90I4 17 DE90I4 18 Generator Stamford UCI274C Winding Group 06 311 311 311 Wattage 86000 90000 9...

Page 27: ...ug the connector back into the DSE 3110 5 Unplug the seven green pin connector containing terminal 1 6 Position 1 already has a wire in it You will have to cut that wire and splice a new wire into the...

Page 28: ...ding those of merchantability and fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or co...

Reviews: