60708-162

4094-00

10

    *************

*****  WARNING  *****

    *************

PERSONAL DANGER - 

These unit are shipped with a 

NEUTRAL TO GROUND BOND INSTALLED. If your system 

already has a neutral to ground bond then you must run a 

separate ground lead to that location AND UNBOND THE 

JUMPER IN THE CONNECTION PANEL.  For additional 

questions refer to the current National Electric Code on 

grounding.

   *************

*****  WARNING  *****

    ************* 

EQUIPMENT DAMAGE

 - 

When installing a Three Phase 240 

volt system be sure you know which lead is the high voltage 

“wild” leg (208 Volt line to neutral). The generator normally 

carries the high voltage on the G2 lead.

 

ENGINE CONTROL PANEL 

LAYOUT MANUAL KEY START

 

A.   FOUR POSITION START SWITCH 

1.   Prehea

t - This position is used on the DE20 and DE30 

only.  With the switch in this position the  glow plugs on the 

engine are activated.

2.  OFF 

- In this position all power to the engine is  

 

turn off and the engine is stopped.

3.  RUN 

- With the switch in this position the fuel solenoid 

and the fuel pump on the engine are activated. A 12 Volt 

signal is also being sent to the voltage regulator on the 

engine alternator to activate it.

4.  START 

- This position on the switch will  activate the 

starter on the engine to start it.

B.  CHECK ENGINE LIGHT

 - This light will come on when the 

low oil pressure switch or the high water temperature sensor 

switches have  been activated on the engine.  This light will also 

come on when you go to start the engine, and stay on until the 

engine has built sufficient oil pressure to open the low oil pressure 

switch.

C.   RUNNING TIME METER 

- This meter records the actual 

hours of engine operation.

D.   25 AMP FUSE

 - This fuse protect all the DC wiring in the 

engine control panel and on the engine.  If this fuse if blown 

nothing will work on the engine.

E.  SAFETY LATCHING RELAY

 - This safety latching relay 

provides the 12 volt DC power to the fuel solenoid and the engine  

alternator field circuit during normal operation.  If the system 

experiences a low oil pressure fault or a high water temperature 

fault this relay will trip disconnecting the fuel solenoid and shutting 

down the engine.  When tripped the button on the panel will 

extend out about 1 inch.  This button must also be held in during 

starting until the check engine light goes out.  

INITIAL START UP 

MANUAL KEY START

   *************

*****  WARNING  *****

    ************* 

EQUIPMENT DAMAGE

 - 

DO NOT jump start these engine 

generator  sets. Starting these units on a low battery or jump 

starting them may cause damage to the engine controls.

Use the following check list to verify correct installation before 

starting the engine:

 

1.  Engine oil.  Fill as required with proper grade/qty.

 

2.  Engine coolant.  Fill as required with proper mixture.

 

3.  Unit mounting base properly bolted down.

 

4.  Clearance for service and maintenance on all sides.

 

5.  Proper fuel line material and size. 

 

6.  All fuel line connections tight.

 

7.  Battery connections clean and tight.

  

8.  Battery fully charged.

  

9.  All AC and DC wiring installed and properly protected.

After completing the above checklist, the engine-generator set is 

ready for the initial start-up test.

STARTING PROCEDURE

1.  Rotate start switch (A) to the preheat position and hold for 10 

seconds. NOTE:  

This step applies to the DE20 & DE30 ONLY.

2.    Rotate the Start Switch (A) to the Run position.  Then while 

depressing the Safety Latching Relay button (E) rotate the switch 

to the Start position.  At this point the starter should engage and 

the unit will start.

Summary of Contents for DE20I4

Page 1: ...INSTALLATION AND OPERATIONS MANUAL with STAMFORD GENERATORS MODELS DE20I4 DE30I4 DE45F4 DE65F4 DE90F4 MANUAL KEY START AND DSE3110 ELECTRIC START ELECTRIC START DIESEL GENERATORS...

Page 2: ...NUMBER________________________ M Spec ______________________________ PURCHASE DATE_______________________ DEALER_______________________________ TABLE OF CONTENTS INTRODUCTION i GUIDE TO PRODUCT SAFET...

Page 3: ...into the earth 2 FIRE HAZARD Diesel fuel presents a hazard of possible explosion and or fire a Do not smoke or use open flame near the generator set b Keep a fire extinguisher nearby and know its prop...

Page 4: ...000 Volts 120 240 120 208 120 240 277 480 Phase single three three three PF 1 0 80 80 80 AMPs 125 104 90 45 Hertz 60 60 60 60 Engine Model Isuzu 4LE TurboCharged Starting System 12 Volt Manual Start M...

Page 5: ...omponents also have their own individual identity plates providing additional information to document build data for warranty and replacement parts Be sure to have the main WINPOWER unit data plate in...

Page 6: ...to the entire standby generator line It is the responsibility of the installing party to follow the lifting equipment s operators manual to prevent injury to personnel and damage to the generator Smal...

Page 7: ...tor discharge These fresh air inlets should also be 1 1 2 to 2 times large than the radiator face The extra air inlet area is required to minimize restriction and to provide combustion air for the eng...

Page 8: ...ine manufacturer s maintenance instructions INSTALLING THE BATTERY CAUTION In the following battery installation procedure check to be sure the engine control is in the stop position This should be yo...

Page 9: ...are tight and coat the terminals and cable ends with dialectic grease WARNING The electrolyte is a diluted sulfuric acid that is harmful to the skin and eyes It is electrically conductive and corrosi...

Page 10: ...60708 162 4094 00 CONTROL BOX AC WIRING...

Page 11: ...77 480 3 45 14 1 0 AWG 80 in lbs kW Voltage PH Amp Wire Capability Lug Torque 45 120 240 1 175 4 AWG 300 MCM 250 in lbs 45 120 208 3 150 4 AWG 300 MCM 250 in lbs 45 120 240 3 150 4 AWG 300 MCM 250 in...

Page 12: ...SE This fuse protect all the DC wiring in the engine control panel and on the engine If this fuse if blown nothing will work on the engine E SAFETY LATCHING RELAY This safety latching relay provides t...

Page 13: ...s the AC voltage reading on the display If this fuse is blown the DSE 3110 will not display a voltage or frequency reading and will shutdown on low voltage or frequency Replacement fuse ATO ATC 2A 250...

Page 14: ...on places the module into its Automatic mode This mode allows the module to control the function of the generator automatically The module will monitor the remote start input and once a start request...

Page 15: ...high water temperature 5 After the engine is up an running the circuit breaker can be closed to power your loads During periods of very cold operation it is best to let the engine warm up for a few s...

Page 16: ...ailed below Press 4 to select the next parameter or 3 to select the previous parameter within the current page When viewing the parameter to be changed press the 1 button The value begins to flash Pre...

Page 17: ...high engine temperature pre alarm setting level after the Safety On timer has expired UNDERSPEED The engine speed has fallen below the underspeed pre alarm setting OVERSPEED The engine speed has rise...

Page 18: ...fective fuel pump 7 Defective fuel solenoid 8 Defective engine harness 9 Improper battery voltage to fuel pump or fuel solenoid ENGINE STARTS AND THEN STOPS AND ALARM LIGHT COMES ON 1 Engine oil press...

Page 19: ...4094 00 60708 162 17 START CONTROL PANEL ENGINE WIRING HARNESS DE20 DE30 KEY START SCHMATIC...

Page 20: ...60708 162 4094 00 18 START CONTROL PANEL ENGINE WIRING HARNESS DE45 DE65 KEY START SCHMATIC...

Page 21: ...4094 00 60708 162 19 DE20 DE30 3110 ELECTRIC START PANEL LEFT BLANK INTENTIONALLY AT THIS TIME...

Page 22: ...60708 162 4094 00 20 86 85 30 87a 87 86 85 30 87a 87 DE45 DE65 DE90 3110 ELECTRIC START PANEL...

Page 23: ...4094 00 60708 162 21 THREE PHASE AC WIRING HIGH AND LOW WYE...

Page 24: ...60708 162 4094 00 22 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING...

Page 25: ...nual Start Oil Filter 2 required 2992544 Pre Fuel filter Water Sep 2992662 Water Sensor 4254020 Fuel Filter Elements 2994048 Air Filter Element 8025818 Alternator Belt 500341810 Alternator 500315943 S...

Page 26: ...r additional oil information Oil Capacity 13 5 Quarts Cooling System 50 50 Mix MODEL DE90I4 3 DE90I4 4 DE90I4 17 DE90I4 18 Generator Stamford UCI274C Winding Group 06 311 311 311 Wattage 86000 90000 9...

Page 27: ...ug the connector back into the DSE 3110 5 Unplug the seven green pin connector containing terminal 1 6 Position 1 already has a wire in it You will have to cut that wire and splice a new wire into the...

Page 28: ...ding those of merchantability and fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or co...

Reviews: