INITIAL START UP 

   *************

*****  WARNING  *****

    ************* 

EQUIPMENT DAMAGE

 - 

DO NOT jump start these engine 

generator  sets. Starting these units on a low battery or 

jump starting them will cause damage to the engine control 

module.

Use the following check list to verify correct installation before 

starting the engine:

 

1.  Engine oil.  Fill as required with proper grade/qty.

 

2.  Engine coolant.  Fill as required with proper mixture.

 

3.  Unit mounting base properly bolted down.

 

4.  Clearance for service and maintenance on all sides.

 

5.  Proper fuel line material and size. 

 

6.  All fuel line connections tight.

 

7.  Battery connections clean and tight.

  

8.  Battery fully charged.

  

9.  All AC and DC wiring installed and properly protected.

After completing the above checklist, the engine-generator set is 

ready for the initial start-up test.

STARTING PROCEDURE

MANUAL MODE

    ****************

*****  WARNING  *****

      **************** 

EQUIPMENT DAMAGE 

-

 BEFORE ATTEMPTING TO START 

THIS UNIT COMPLETE YOUR PRE-START CHECKLIST AND 

ENSURE THE GENERATOR MAINLINE CIRCUIT BREAKER IS 

IN THE PROPER POSITION PRIOR TO STARTING.  STARTING 

THIS UNIT WITHOUT IT PROPERLY CONNECTED CAN 

CAUSE SERIOUS PERSONAL INJURY OR EQUIPMENT 

DAMAGE.

1.  Press and release the red Stop/Reset button.

2.  Press and release the green Start Engine button. The engine 

generator set will crank and start automatically.  If the engine fails 

to start it will display a fault code and the common alarm indicator 

will start blinking.  See the fault code in the Appendix portion of 

this manual.

3.  With the unit running smoothly, check the no load voltage and 

frequency of the generator output.

4.  Once the unit is running and the safety on time has elapsed 

the engine monitoring switches are active for low oil pressure and 

high water temperature.

5. After the engine is up an running the circuit breaker can be 

closed to power your loads.  During periods of very cold operation 

it is best to let the engine warm up for a few seconds before 

applying the load.

6.  When stopping the unit it is best to turn off all the loads before 

pressing the stop button.  This prevents your loads from getting 

low voltage while still running during unit shutdown.

DSE 3110 ENGINE CONTROL

PROTECTIONS

When an alarm is present, the Common alarm LED if configured 

will illuminate.  

The LCD display will show an icon to indicate 

the failure.

WARNINGS

Warnings are non-critical alarm conditions and do not affect 

the operation of the generator system, they serve to draw the 

operator’s attention to an undesirable condition.  Warning alarms 

are self-resetting when the fault condition is removed.  The icon 

will appear steady in the display.

SHUTDOWNS

Shutdowns are critical alarm conditions that stop the engine and 

draw the operator’s attention to an undesirable condition.  Shut-

down alarms are latching.  

The fault must be removed and the 

STOP/RESET button pressed to reset the module.  

The icon 

will appear flashing in the display.

MODULE DISPLAY

TIMER ICON

When the module is controlling the engine (starting and stop-

ping) an animated timer icon will be displayed in the icon area to 

indicate that a timer is active, for example cranking time, crank 

rest, etc.

STOPPED ICON

When there are no alarms present, an icon will be displayed to 

indicate the engine is stopped and what mode the unit is in.

  Stop Mode           Auto Mode            Manual Mode

RUNNING ICON

When there are no alarms present, an animated icon is displayed 

to indicate the engine is running.

USB ICON

When a USB connection is made to the module the USB icon is 

displayed.

MEMORY CORRUPTION

If either the config file or engine file becomes 

corrupted the unit will display the following icon. 

  

Summary of Contents for DE20I4

Page 1: ...INSTALLATION AND OPERATIONS MANUAL with STAMFORD GENERATORS MODELS DE20I4 DE30I4 DE45F4 DE65F4 DE90F4 MANUAL KEY START AND DSE3110 ELECTRIC START ELECTRIC START DIESEL GENERATORS...

Page 2: ...NUMBER________________________ M Spec ______________________________ PURCHASE DATE_______________________ DEALER_______________________________ TABLE OF CONTENTS INTRODUCTION i GUIDE TO PRODUCT SAFET...

Page 3: ...into the earth 2 FIRE HAZARD Diesel fuel presents a hazard of possible explosion and or fire a Do not smoke or use open flame near the generator set b Keep a fire extinguisher nearby and know its prop...

Page 4: ...000 Volts 120 240 120 208 120 240 277 480 Phase single three three three PF 1 0 80 80 80 AMPs 125 104 90 45 Hertz 60 60 60 60 Engine Model Isuzu 4LE TurboCharged Starting System 12 Volt Manual Start M...

Page 5: ...omponents also have their own individual identity plates providing additional information to document build data for warranty and replacement parts Be sure to have the main WINPOWER unit data plate in...

Page 6: ...to the entire standby generator line It is the responsibility of the installing party to follow the lifting equipment s operators manual to prevent injury to personnel and damage to the generator Smal...

Page 7: ...tor discharge These fresh air inlets should also be 1 1 2 to 2 times large than the radiator face The extra air inlet area is required to minimize restriction and to provide combustion air for the eng...

Page 8: ...ine manufacturer s maintenance instructions INSTALLING THE BATTERY CAUTION In the following battery installation procedure check to be sure the engine control is in the stop position This should be yo...

Page 9: ...are tight and coat the terminals and cable ends with dialectic grease WARNING The electrolyte is a diluted sulfuric acid that is harmful to the skin and eyes It is electrically conductive and corrosi...

Page 10: ...60708 162 4094 00 CONTROL BOX AC WIRING...

Page 11: ...77 480 3 45 14 1 0 AWG 80 in lbs kW Voltage PH Amp Wire Capability Lug Torque 45 120 240 1 175 4 AWG 300 MCM 250 in lbs 45 120 208 3 150 4 AWG 300 MCM 250 in lbs 45 120 240 3 150 4 AWG 300 MCM 250 in...

Page 12: ...SE This fuse protect all the DC wiring in the engine control panel and on the engine If this fuse if blown nothing will work on the engine E SAFETY LATCHING RELAY This safety latching relay provides t...

Page 13: ...s the AC voltage reading on the display If this fuse is blown the DSE 3110 will not display a voltage or frequency reading and will shutdown on low voltage or frequency Replacement fuse ATO ATC 2A 250...

Page 14: ...on places the module into its Automatic mode This mode allows the module to control the function of the generator automatically The module will monitor the remote start input and once a start request...

Page 15: ...high water temperature 5 After the engine is up an running the circuit breaker can be closed to power your loads During periods of very cold operation it is best to let the engine warm up for a few s...

Page 16: ...ailed below Press 4 to select the next parameter or 3 to select the previous parameter within the current page When viewing the parameter to be changed press the 1 button The value begins to flash Pre...

Page 17: ...high engine temperature pre alarm setting level after the Safety On timer has expired UNDERSPEED The engine speed has fallen below the underspeed pre alarm setting OVERSPEED The engine speed has rise...

Page 18: ...fective fuel pump 7 Defective fuel solenoid 8 Defective engine harness 9 Improper battery voltage to fuel pump or fuel solenoid ENGINE STARTS AND THEN STOPS AND ALARM LIGHT COMES ON 1 Engine oil press...

Page 19: ...4094 00 60708 162 17 START CONTROL PANEL ENGINE WIRING HARNESS DE20 DE30 KEY START SCHMATIC...

Page 20: ...60708 162 4094 00 18 START CONTROL PANEL ENGINE WIRING HARNESS DE45 DE65 KEY START SCHMATIC...

Page 21: ...4094 00 60708 162 19 DE20 DE30 3110 ELECTRIC START PANEL LEFT BLANK INTENTIONALLY AT THIS TIME...

Page 22: ...60708 162 4094 00 20 86 85 30 87a 87 86 85 30 87a 87 DE45 DE65 DE90 3110 ELECTRIC START PANEL...

Page 23: ...4094 00 60708 162 21 THREE PHASE AC WIRING HIGH AND LOW WYE...

Page 24: ...60708 162 4094 00 22 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING...

Page 25: ...nual Start Oil Filter 2 required 2992544 Pre Fuel filter Water Sep 2992662 Water Sensor 4254020 Fuel Filter Elements 2994048 Air Filter Element 8025818 Alternator Belt 500341810 Alternator 500315943 S...

Page 26: ...r additional oil information Oil Capacity 13 5 Quarts Cooling System 50 50 Mix MODEL DE90I4 3 DE90I4 4 DE90I4 17 DE90I4 18 Generator Stamford UCI274C Winding Group 06 311 311 311 Wattage 86000 90000 9...

Page 27: ...ug the connector back into the DSE 3110 5 Unplug the seven green pin connector containing terminal 1 6 Position 1 already has a wire in it You will have to cut that wire and splice a new wire into the...

Page 28: ...ding those of merchantability and fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or co...

Reviews: