4094-00
60708-162
1
INITIAL START UP
*************
***** WARNING *****
*************
EQUIPMENT DAMAGE
-
DO NOT jump start these engine
generator sets. Starting these units on a low battery or
jump starting them will cause damage to the engine control
module.
Use the following check list to verify correct installation before
starting the engine:
1. Engine oil. Fill as required with proper grade/qty.
2. Engine coolant. Fill as required with proper mixture.
3. Unit mounting base properly bolted down.
4. Clearance for service and maintenance on all sides.
5. Proper fuel line material and size.
6. All fuel line connections tight.
7. Battery connections clean and tight.
8. Battery fully charged.
9. All AC and DC wiring installed and properly protected.
After completing the above checklist, the engine-generator set is
ready for the initial start-up test.
STARTING PROCEDURE
MANUAL MODE
****************
***** WARNING *****
****************
EQUIPMENT DAMAGE
-
BEFORE ATTEMPTING TO START
THIS UNIT COMPLETE YOUR PRE-START CHECKLIST AND
ENSURE THE GENERATOR MAINLINE CIRCUIT BREAKER IS
IN THE PROPER POSITION PRIOR TO STARTING. STARTING
THIS UNIT WITHOUT IT PROPERLY CONNECTED CAN
CAUSE SERIOUS PERSONAL INJURY OR EQUIPMENT
DAMAGE.
1. Press and release the red Stop/Reset button.
2. Press and release the green Start Engine button. The engine
generator set will crank and start automatically. If the engine fails
to start it will display a fault code and the common alarm indicator
will start blinking. See the fault code in the Appendix portion of
this manual.
3. With the unit running smoothly, check the no load voltage and
frequency of the generator output.
4. Once the unit is running and the safety on time has elapsed
the engine monitoring switches are active for low oil pressure and
high water temperature.
5. After the engine is up an running the circuit breaker can be
closed to power your loads. During periods of very cold operation
it is best to let the engine warm up for a few seconds before
applying the load.
6. When stopping the unit it is best to turn off all the loads before
pressing the stop button. This prevents your loads from getting
low voltage while still running during unit shutdown.
DSE 3110 ENGINE CONTROL
PROTECTIONS
When an alarm is present, the Common alarm LED if configured
will illuminate.
The LCD display will show an icon to indicate
the failure.
WARNINGS
Warnings are non-critical alarm conditions and do not affect
the operation of the generator system, they serve to draw the
operator’s attention to an undesirable condition. Warning alarms
are self-resetting when the fault condition is removed. The icon
will appear steady in the display.
SHUTDOWNS
Shutdowns are critical alarm conditions that stop the engine and
draw the operator’s attention to an undesirable condition. Shut-
down alarms are latching.
The fault must be removed and the
STOP/RESET button pressed to reset the module.
The icon
will appear flashing in the display.
MODULE DISPLAY
TIMER ICON
When the module is controlling the engine (starting and stop-
ping) an animated timer icon will be displayed in the icon area to
indicate that a timer is active, for example cranking time, crank
rest, etc.
STOPPED ICON
When there are no alarms present, an icon will be displayed to
indicate the engine is stopped and what mode the unit is in.
Stop Mode Auto Mode Manual Mode
RUNNING ICON
When there are no alarms present, an animated icon is displayed
to indicate the engine is running.
USB ICON
When a USB connection is made to the module the USB icon is
displayed.
MEMORY CORRUPTION
If either the config file or engine file becomes
corrupted the unit will display the following icon.
Summary of Contents for DE20I4
Page 10: ...60708 162 4094 00 CONTROL BOX AC WIRING...
Page 19: ...4094 00 60708 162 17 START CONTROL PANEL ENGINE WIRING HARNESS DE20 DE30 KEY START SCHMATIC...
Page 20: ...60708 162 4094 00 18 START CONTROL PANEL ENGINE WIRING HARNESS DE45 DE65 KEY START SCHMATIC...
Page 21: ...4094 00 60708 162 19 DE20 DE30 3110 ELECTRIC START PANEL LEFT BLANK INTENTIONALLY AT THIS TIME...
Page 22: ...60708 162 4094 00 20 86 85 30 87a 87 86 85 30 87a 87 DE45 DE65 DE90 3110 ELECTRIC START PANEL...
Page 23: ...4094 00 60708 162 21 THREE PHASE AC WIRING HIGH AND LOW WYE...
Page 24: ...60708 162 4094 00 22 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING...