Installation 

 

____________________________________________________________________________ 

 

Cable routing 

 
Observe the safety information on page 2. 
For cable routing we recommend the use of fire protected cables retaining their function E90 or E30. 
However, this has to be agreed with the Engineer or, if necessary, with the local fire protection department. 
Do not reduce the cable cross sections specified in the cable lengths table. 
All cables of the control centre (except the mains supply cable) carry 24V DC and have to be routed separate 
from the mains supply cable. 
Adhere to the pertinent 

national and local regulations 

when routing the cables. 

Do not use the green/yellow conductor. 
Ensure that the mains cable can be switched via an external or customer-supplied two-pole switch element or 
a switch element controlling all poles. 
 

Smoke unit installation 

 
Note that the control centre has to be installed in a dry room.  
 

Concealed housing 

Refer to the sketch below for the installation position 

 

Open central control and remove the housing 
top section (door) from the housing bottom section. 
Fasten the housing bottom section in the wall cut-out 
(cut-out dimension 335 x 350 x 95) and 
refit the housing top section. 
Also possibility for surface mounting with the included frame. 

 
 

Installation of the Break glass unit, ventilation buttons and detectors 

 
Ensure that the Break glass unit and the ventilation buttons are visible and well accessible.  
Do not install behind protruding walls, door panels or hidden by the building structure. 
Note: Installation height of the Break glass unit = 1.4 m above floor. 
Install the automatic detectors in accordance with their enclosed instructions. 
 
 

Installation 

 
Lead the connection cables into the housing of the control centre from above. 
All connection terminals (except the mains terminals) are of the plug-in type. 
Connect the connection cables in accordance with the terminal plan. Ensure that the connections are made 
correctly. 
Incorrect clamping, mixing up numbers or colours could lead to malfunctions of the central control or of the 
external components.  
 
Ensure that the electrical cables are always routed according to the valid national and local regulations of the 
individual country. 
 
 

Summary of Contents for WSC 304 6102

Page 1: ...able of contents Safety information Operating elements and fuse review Technical data Installation Cable lengths table Cable plan Standard wiring diagram Various wiring diagrams Commissioning Maintena...

Page 2: ...e insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of smoke extraction sys...

Page 3: ...Operating elements and fuse review ____________________________________________________________________________ 3...

Page 4: ...moke control unit the red LED in the break glass unit and the red LED at the tripped automatic detector extinguish Resetting a trip caused by high temperature The smoke extraction system can be closed...

Page 5: ...rated in the button Ventilation closed The actuators close after pressing the CLOSED button Display The ventilation open LED in the ventilation button has extinguished only with LED integrated in the...

Page 6: ...at there is no fault An alarm signal has first priority SW 1 2 ON Forwarding the alarm signal WSA 301 After 3 min it will stop SW 1 2 OFF Forwarding the alarm signal WSA 301 as long as the alarm is tr...

Page 7: ...terminal for 2 wire BUS cable for the feedback of malfunctions in cascaded control units to the break glass unit connected to the master smoke control unit Alarm message 1 x change over contact max l...

Page 8: ...y every 2 min Review of fuses Mains 630mA slow blow Motor 4 A slow blow Battery 630mA medium slow blow Type of connection to external Mains screw terminal plug screw terminals 0 5 2 5qmm Cable monitor...

Page 9: ...control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 350 x 95 and refit the housing top sectio...

Page 10: ...imum cable length always routed from the central smoke control unit to the last junction box Actuating current Sum of all motor currents per group module Note Do not use the green yellow wire Per moto...

Page 11: ...Cable plan ____________________________________________________________________________ 11...

Page 12: ..._____________________________________________________ 12 WLA 330 WLA331 WSA 300 WSC 304 6102 WSK 320 WSK 330 First or secundary Break glass unit If only one break glass unit usa a main break glass uni...

Page 13: ...Various wiring diagrams ____________________________________________________________________________ 13...

Page 14: ...from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the wiring diagram then co...

Page 15: ...b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c The ventilation butto...

Page 16: ...and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install original spare parts C...

Reviews: