Commisioning
____________________________________________________________________________
14
When error message occur, please refer to chapter Operating elements and fuse review.
An acoustic message only occurs in the Break glass unit with the door closed or the door contact switch
pressed!
1)
2)
Adhere to the relevant regulations! Externally disconnect the mains voltage.
3)
4)
a) Closely observe the actuators during opening and closing. They must not be impaired in any
position by the building structure. Also the motor connection cables
must not be subject to pulling or crushing.
5)
6)
The control centre is completely installed, without the operating voltage applied
only
With mains voltage, without accumulator
With mains voltage, with accumulator
Ventilation button
Break glass unit
Break glass unit (secondary)
a) Check all mechanical and electrical components for damage.
b) Check the DIP slide switches in the control centre for their correct (required) position.
c) Check all screw and plug connections for tightness and/or firm seating.
d) Check that all external components are installed.
Actuators:
Is the final module at the last or only actuator inserted?
Automatic detectors:
Is the active end module at the last or only detector inserted?
Manual detectors:
Is the jumper
inserted in the last or only operating panel?
a) Connect the mains cables and reapply the mains voltage.
b) The mains LED is ON, the operating LED is OFF, the accumulator LED is ON. The malfunction message at
the operating panels is ON.
a) Remove the protection film of the lateral adhesive tape for the 1.9 Ah battery, and firmly press the two
batteries together according to the picture (next page).
b) Remove the protection film from one face of the supplied foam rubber. Glue each foam rubber to the
bottom side of the accumulators. Connect the accumulators to the black accumulator bridge according to
the wiring diagram, then connect the red and the blue connection cable to the red and the black flat plug.
Remove the bottom protection film of the foam rubber and insert the batteries in the control unit according
to figure 1, and firmly press down to the housing bottom!
c) Plug the red connection cable to the + and the blue connection to the flat plug of the control unit. Note:
Check correct polarity!
d) The operating LED is ON, the accumulator LED is OFF. The malfunction message at the operating panels
is OFF.
b) Briefly actuate the Open button to have the actuators move open up to the final position. With the SW2/2
=ON (hold-to-run) setting, the actuators only move as long as the button is pressed. The OPEN display (if
existing) in the button is ON.
c)
Briefly actuate the CLOSED button, the actuators close. The Open display is OFF.
d) Press both buttons simultaneously while running, this corresponds to stop. The ventilation Open display is
ON, the actuators stop.
e) Briefly press the Closed button again, the actuators fully close, the Open display is OFF.
a) Open the door and press the red Open button. The actuators move open through to the end position. The
red alarm LED (also in the control unit) is ON, at the same time a permanent acoustic signal sounds (door
contact pressed!).
b) While running, press the Closed button at the ventilation button, then press both buttons, the actuators
must neither close nor stop!
c) Press the reset/Closed button in the break glass unit. The actuators close through to the end position. The
ventilation function is released again. The red alarm LED (also in the control unit) and the signal generator
are OFF.
a) Check as described under 5). „Operation“, „Malfunction“ and the acoustic signal are missing!