Technical data

 

____________________________________________________________________________ 

 

Connection possibilities: 

1)  Actuators with a total power consumption of max. 4A 
2)  Smoke detectors, up to 10 pieces in 1 sensor group 
 

Optical smoke detector and/or thermo-differential sensor  

 

and/or heat max. sensor                                                            WSA 300, WSA 310 

3)  Break glass units (main), up to 4 per sensor group                   WSK 320 000X 
4)  Break glass units (secondary), up to 15                                     WSK 330 000X 
5)  Ventilation buttons with 

‘indicator, up to 15,  

 

any number without 

‘open’ indicator                                           WSK 100 1161 

6)  Wind/rain detector with potential free close contact                   WLA 330 01, WLA 331 01 
7)  SHE activation on potential free 

ASV contact in the smoke sensor entrance                                WSA 306 install 

 

Operation / LED diagnose 

Pushing the reset button on the circuit board the SHE activation is reset and the actuators closes. 
 

Setting possibilities via slide switch SW1

 

SW 1/1 = ON 

Inspection indication activated 

SW 1/1 = OFF 

Inspection indication not activated. After activation only a coded deactivation is possible 

 
To show the activation the LED will flash 10 sec. If this time SW1/1 is once again set on OFF, the prioritised 
activation is cancelled. 
After a period of 12 month the inspection indication will be activated: the yellow fault LED in the main break 
glass unit will flash and the audible fault alarm will sound. The green operating LED will still flash to show that 
there is no fault. An alarm signal has first priority. 
 
SW 1/2 = ON 

Forwarding the alarm signal (WSA 301). After 3 min. it will stop.  

SW 1/2 = OFF 

Forwarding the alarm signal (WSA 301) as long as the alarm is trigged. 

 

Setting possibilities via slide switch SW2

 

 
SW 2/1 = ON 

The SHE alarm trips when malfunction signal from actuator, smoke sensor, break glass 
unit, max. temperature sensor.

 

SW 2/1 = OFF 

No SHE alarm tripped when malfunction signal. Malfunction only shown on the LEDs. 

 
SW 2/2 = ON 

The actuators 

only

 open for as long as the ventilation button is pressed (dead man control) 

SW 2/2 = OF 

The actuators opens all up when the ventilation buttons is pressed (self hold) 

 

Diagnosis / monitoring in the control unit and fault elimination 

 

LED on the 

circuit board 

Function is OK 

Malfunction 

Diagnose 

Mains (green) 

Lit 

Off 

Check mains voltage and mains fuse 

Operation (green) 

Lit 

Off 

Check all functions 

Battery/load control 
(yellow) 

Off 

Flashes when main failure 
or when charging voltage 
is under 26V. 
Lits when 
battery no connection,  
battery fuse defect, 
Battery voltage under 19V 

Check main fuse and charging 
voltage. 
 
 
Check battery connection. 
Check battery fuse. 
Check battery voltage 

Motor circuit (yellow) 

Off 

Flashes when interrupted  Check actuator fuse and  

actuator end module 

Break glass unit (yellow) 

Off 

Flashes when interrupted. 
Lits when short circuit.  

Check wiring and jumper J1 in the last 
or only break glass unit. 

Smoke detector (yellow) 

Off 

Flashes when interrupted. 
Lits when short circuit 

Check wiring and the active end 
module. 

 
Battery and actuator circuit malfunction be about 8 sec. delayed. 
 
 
 

Summary of Contents for WSC 304 6102

Page 1: ...able of contents Safety information Operating elements and fuse review Technical data Installation Cable lengths table Cable plan Standard wiring diagram Various wiring diagrams Commissioning Maintena...

Page 2: ...e insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of smoke extraction sys...

Page 3: ...Operating elements and fuse review ____________________________________________________________________________ 3...

Page 4: ...moke control unit the red LED in the break glass unit and the red LED at the tripped automatic detector extinguish Resetting a trip caused by high temperature The smoke extraction system can be closed...

Page 5: ...rated in the button Ventilation closed The actuators close after pressing the CLOSED button Display The ventilation open LED in the ventilation button has extinguished only with LED integrated in the...

Page 6: ...at there is no fault An alarm signal has first priority SW 1 2 ON Forwarding the alarm signal WSA 301 After 3 min it will stop SW 1 2 OFF Forwarding the alarm signal WSA 301 as long as the alarm is tr...

Page 7: ...terminal for 2 wire BUS cable for the feedback of malfunctions in cascaded control units to the break glass unit connected to the master smoke control unit Alarm message 1 x change over contact max l...

Page 8: ...y every 2 min Review of fuses Mains 630mA slow blow Motor 4 A slow blow Battery 630mA medium slow blow Type of connection to external Mains screw terminal plug screw terminals 0 5 2 5qmm Cable monitor...

Page 9: ...control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 350 x 95 and refit the housing top sectio...

Page 10: ...imum cable length always routed from the central smoke control unit to the last junction box Actuating current Sum of all motor currents per group module Note Do not use the green yellow wire Per moto...

Page 11: ...Cable plan ____________________________________________________________________________ 11...

Page 12: ..._____________________________________________________ 12 WLA 330 WLA331 WSA 300 WSC 304 6102 WSK 320 WSK 330 First or secundary Break glass unit If only one break glass unit usa a main break glass uni...

Page 13: ...Various wiring diagrams ____________________________________________________________________________ 13...

Page 14: ...from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the wiring diagram then co...

Page 15: ...b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c The ventilation butto...

Page 16: ...and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install original spare parts C...