Cascading smoke control units: 

The smoke control units can be cascaded by a monitored 2 wire connection from the alarm module of the 
master smoke control unit to the smoke detector input of the slave central panel. 
A malfunction in the cascaded smoke control units is detected via the 2 wire BUS cable. The malfunction is 
only displayed in the corresponding smoke control unit and in the break glass unit connected to the master 
smoke control unit.: 
 
 
 

Ventilation functions: 

 

Ventilation OPEN: 

With the dead man's circuit activated (SW2/2 = ON), the actuators only move open for as long as the OPEN 
button of the ventilation button is kept pressed. 
If no dead man's function is activated (SW2/2 = OFF), the actuators open after pressing the OPEN button 
(self hold). 

Display:

 The ventilation open LED in the ventilation button is lit (only with LED integrated in the button). 

 

Ventilation stop: 

The actuators stop when both buttons are pressed. 

Display:

 The ventilation open LED in the ventilation button remains lit (only with LED integrated in the button). 

 

Ventilation closed: 

The actuators close after pressing the CLOSED button. 

Display: 

The ventilation open LED in the ventilation button has extinguished (only with LED integrated in the 

button). 
 

Option: Ventilation time module 

Timemodule WSA 303: 
Time to be set 

between 1 and 30 min. Once this time has elapsed, the actuators close after ventilation „OPEN“ 

or ventilation „STOP“. This function is not operative if the setting potentiometer is on the right-hand stop. 
 

Wind/rain CLOSE: 

The actuators close when the wind/rain sensor has tripped (potential free contact in the sensor switches). The 
ventilation functions are out of operation as long as a tripped situation is pending. 
The tripped signal is shown with the green wind/rain LED. 

Alarm tripping has 1. priority. 
 
Option: Transmission of the wind/rain signal 

Module WSA 302: 
The trip signal of the wind/rain sensor can be transmitted potential free to the next smoke control unit. 
 

CLOSE after a power failure: 

2 minutes after a power failure actuators opened for natural ventilation will automatically. 
In the event of alarm, this function will be out of operation. 

 
 
 
General information: 

 

EMC protection: 

All inputs and outputs are protected from coupled in interferences. 
 

Short-circuit protection: 

All outputs are protected against short-circuit and overload. 
 

 

 
 

Summary of Contents for WSC 304 6102

Page 1: ...able of contents Safety information Operating elements and fuse review Technical data Installation Cable lengths table Cable plan Standard wiring diagram Various wiring diagrams Commissioning Maintena...

Page 2: ...e insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of smoke extraction sys...

Page 3: ...Operating elements and fuse review ____________________________________________________________________________ 3...

Page 4: ...moke control unit the red LED in the break glass unit and the red LED at the tripped automatic detector extinguish Resetting a trip caused by high temperature The smoke extraction system can be closed...

Page 5: ...rated in the button Ventilation closed The actuators close after pressing the CLOSED button Display The ventilation open LED in the ventilation button has extinguished only with LED integrated in the...

Page 6: ...at there is no fault An alarm signal has first priority SW 1 2 ON Forwarding the alarm signal WSA 301 After 3 min it will stop SW 1 2 OFF Forwarding the alarm signal WSA 301 as long as the alarm is tr...

Page 7: ...terminal for 2 wire BUS cable for the feedback of malfunctions in cascaded control units to the break glass unit connected to the master smoke control unit Alarm message 1 x change over contact max l...

Page 8: ...y every 2 min Review of fuses Mains 630mA slow blow Motor 4 A slow blow Battery 630mA medium slow blow Type of connection to external Mains screw terminal plug screw terminals 0 5 2 5qmm Cable monitor...

Page 9: ...control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 350 x 95 and refit the housing top sectio...

Page 10: ...imum cable length always routed from the central smoke control unit to the last junction box Actuating current Sum of all motor currents per group module Note Do not use the green yellow wire Per moto...

Page 11: ...Cable plan ____________________________________________________________________________ 11...

Page 12: ..._____________________________________________________ 12 WLA 330 WLA331 WSA 300 WSC 304 6102 WSK 320 WSK 330 First or secundary Break glass unit If only one break glass unit usa a main break glass uni...

Page 13: ...Various wiring diagrams ____________________________________________________________________________ 13...

Page 14: ...from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the wiring diagram then co...

Page 15: ...b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c The ventilation butto...

Page 16: ...and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install original spare parts C...

Reviews: