Technical data
____________________________________________________________________________
8
Supply voltage
230V AC / 50Hz (+10% / -15%)
Safety transformer
According EN 61558
Mains amperage
Max. 100VA
Motor output voltage
Load at actuator output
0A
4A
Main
supply
voltage
207V
25V DC
18V DC
230V
28V DC
21V DC
253V
31V DC
24V DC
Emergency power supply batteries
2x 12V / 1,9Ah. Lifetime 4 years.
Charging unit: Charging voltage
26,5V to 29V
………………………… ….. Charging current
350mA, current limited
Operating duration (emergency power supply )
72 hours if batteries are fully charged (1,9Ah)
Current load of the actuators
Max. 4A
Current load of the smoke unit
(batteries, surweillence, periphery)
Max. 0,7A
Switch-on duration
40% ED
Reopening the actuators
During the first 30 min. after a SHE-trig the actuators
cyclically every 2 min.
Review of fuses
Mains 630mA slow-blow
Motor 4 A slow-blow
Battery 630mA medium slow-blow
Type of connection to external
Mains screw terminal / plug-screw terminals / 0.5-
2.5qmm
Cable monitoring
Automatic detectors (detector circuit with active end
module), break glass unit (detector circuit with end
resistor), actuators (with motor end module), batteries
(cyclic measurement)
Message Alarm trip / malfunction
Optically alternating or steady signals by LED's.
Operating and alarm tripping = steady signal.
Malfunction of battery, actuator, break glass unit and
smoke detector in the event of an interruption =
alternating, in the event of a short circuit = steady
signal
Temperature
-5°C - 40°C.
Max. 90% relative humidity (not condensing)
Protection type
IP 30
Housing
Plastic house type UK 511 with metal door.
Build in or surface mounted (with plastic frame).
Protection class II.
Dimensions (WxHxD) 335x350x95mm.
Cut-out dimension hole (WxDxH) 335 x 350 x 95mm.
Upgradeable with 1,9Ah to 2,2Ah batteries.