WIMO 6CP10
Measuring and monitoring unit
Technical description
Wimotec Ltd
24
Wimotec 24h support phone +358 (0)20 753 3264
WM6CP10.EN001
5.
Technical data
5.1.
Connections
5.1.1.
Measuring circuitry
Rated current I
n
5 A
- Current measuring range
0-5 A
- Thermal withstand
6 A (continuously)
25 A (for 10 s)
100 A (for 1 s)
- Burden
< 0.1 VA
Rated current I
0n
50 mA
- Current measuring range
0…100 mA
Rated voltage U
n
230 V ac
- Voltage measuring range
90 – 265 V ac
- Continuous voltage withstand
275 V ac
- Burden
< 0.5 VA
Rated frequency f
n
50
Hz
- Frequency measuring range
45 – 65 Hz
Terminal block:
Maximum wire dimension:
- Solid or stranded wire
2,5 mm
2
(13-14 AWG)
5.1.2.
Auxiliary voltage
Type A (standard)
100 - 240 V ac
110 - 330 V dc
Rated voltage U
aux
110/120/220/240 V ac
Power consumption
< 10 W (normal conditions)
< 15 W (output relay activated)
Max. permitted interruption time
< 15 ms (230 V ac)
Terminal block:
Maximum wire dimension:
- Phoenix MVSTBW or equivalent
2.5 mm
2
(13-14 AWG)
5.1.3.
Digital inputs
Internal operating voltage
Number of inputs
3
Internal operating voltage
12 V dc
Current drain when active (max.)
Approx. 5 mA
Current drain, average value
< 2,5 mA
Terminal block:
Maximum wire dimension:
- Phoenix MVSTBW or equivalent
2.5 mm
2
(13-14 AWG)