Measuring and monitoring unit
Operation and configuration
WIMO 6CP10
WM6CP10.EN001
Wimotec 24h support phone +358 (0)20 753 3264
17
Value Menu/Submenu
Description
Time
U/ VOLT INT SETTING
Hours-minutes-seconds
Event
U/ VOLT INT SETTING
Enabled
I_On
U/ VOLT INT SETTING
Interrupt on event
I_Off
U/ VOLT INT SETTING
Interrupt off event
Figure 4.2-1. Example of harmonics bar display
4.3.
Operation indicators
LED indicator
Meaning
Measure/ Remarks
Power LED lit
The auxiliary power has
been switched on
Normal operation state
Alarm LED lit
One or several signals of
the output relay matrix
have been assigned to
output Al and the output
has been activated by one
of the signals.
The LED is switched off
when the signal that
caused output Al to
activate, e.g. the START
signal, is reset. The
resetting depends on the
type of configuration,
connected or latched.
Resetting latched alarm indicator
The alarm indicator can be given a latching function in the
configuration.
There are several ways to reset latched alarm indicator:
•
From the alarm list, move back to the initial display by
pushing the CANCEL key for approx. 3 s. Then reset the
latched alarm indicator by pushing the ENTER key.
•
Acknowledge each event in the alarm list one by one by
pushing the ENTER key equivalent times. Then, in the
initial display, reset the latched alarm indicator by pushing
the ENTER key.
The latched alarm indicator can also be reset via a remote
communication bus or via a digital input configured for that
purpose.