WIMO 6CP10
Measuring and monitoring unit
Technical description
Wimotec Ltd
6
Wimotec 24h support phone +358 (0)20 753 3264
WM6CP10.EN001
2.2.
Programmable stage
WIMO 6CP10 has eight identical programmable stages
(PROGRAMMABLE STAGE 1-8). All programmable stages can
be enabled or disabled one by one from the menu to fit the
intended application. All the enabled programmable stages
have the following programmable parameters:
•
Link: link to a measured or calculated value, see table
below.
•
Cmp: mode (< or >)
•
Pick-up: alarm limit of the stage (the setting range and the
unit depend on the signal)
•
t: operation delay 0.08 - 300.0 s, step 0.01 s or 0.02 s
•
Hyster: hysteresis 0.2 – 10.0%, step 0.1%
•
NoCmp: no compare limit (visible only for active < mode)
Programmable stage link signals
Alarm stages link signals
Interval
P, Q, S, f, P.F, cos
ϕ
, tan
ϕ
Selectable
Prms, Qrms, Srms
10ms, 20ms
IL1 – IL3, IL, IL max of IL1 – IL3
or 100ms
Io, Iocalc, I1, I2, I2/I1, I2/In
U12, U23, U31, Uline
UL1 – UL3, Uphase
U1, U2, U2/U1
THDIL1, THDIL2, THDIL3, THDUa,THDUb, THDUc
The outputs of the programmable stages can control output
relay A1 and alarm LED, see Figure 2.2-1 and Figure 2.2-2.
In
Ref
Mode
Start
A1
Delay
I, U, P, Q, S, f,
THD
cos
j
Set limit value
Set delay 0.08 - 300s
basicalarmstage
Mode Select
>
<
Figure 2.2-1 Principle of programmable stage