WIMO 6CP10
Measuring and monitoring unit
Technical description
Wimotec Ltd
12
Wimotec 24h support phone +358 (0)20 753 3264
WM6CP10.EN001
Parameter Value Unit Description
Time
s
Duration of the sag/swell
Min1
%Un Minimum voltage value during
the sag/swell in the input 1
Min2
%Un Minimum voltage value during
the sag/swell in the input 2
Min3
%Un Minimum voltage value during
the sag/swell in the input 3
Ave1
%Un Average voltage value during the
sag/swell in the input 1
Ave2
%Un Average voltage value during the
sag/swell in the input 2
Ave3
%Un Average voltage value during the
sag/swell in the input 3
Max1
%Un Maximum voltage value during
the sag/swell in the input 1
Max2
%Un Maximum voltage value during
the sag/swell in the input 2
Recorded
values
Max3
%Un Maximum voltage value during
the sag/swell in the input 3
2.4.
Control functions
2.4.1.
Local/Remote selection
In Local mode, the output relay can be controlled via a local
HMI, but it cannot be controlled via a remote serial
communication interface.
In Remote mode, the output relay cannot be controlled via a
local HMI, but it can be controlled via a remote serial
communication interface.
The selection of the Local/Remote mode is done by using a local
HMI, or via one selectable digital input. The digital input is
normally used to change a whole station to a local or remote
mode. The selection of the L/R digital input is done in the
“Objects” menu of the VAMPSET software.
NOTE!
A password is not required for a remote control operation.
2.5.
Disturbance recorder
The disturbance recorder can be used to record all the
measured signals, that is, currents, voltages and the status
information of digital inputs (DI) and digital output (DO).
At the maximum, there can be 5 recordings, and the maximum
selection of channels in one recording is 12 (limited in
waveform recording). The digital inputs reserve one channel
(includes all the inputs). Also the digital output reserves one
channel.