en
Jockey pump switchgear
70
WILO SE 2020-12
CODE
COMMAND
ACCESS
DESCRIPTION
C13
Reload parameters from backup
memory
Advanced
Transfers the parameters saved in the backup memory to the active
settings memory.
C14
I/O forcing
Advanced
Enables the test mode that allows you to manually energise any output.
NOTICE:
In this mode, the responsibility for controlling the outputs is com-
pletely entrusted to the end-user.
C15
Offset adjustment resistive
sensors
Advanced
Allows resistive sensors to be calibrated by adding/cutting an Ohm
value to the resistance measured by the resistive sensors to com-
pensate for cable length or resistance offset. The calibration is done by
displaying the measured value in engineering quantities.
C16
PLC program reset
Advanced
Clears the program with PLC logic from the internal memory
Once you have selected the desired command, press
to execute it. The instru-
ment will ask for confirmation. Pressing again
the command will be executed.
To cancel the execution of a selected command press STOP. To exit the command
menu press STOP.
11
Jockey pump switchgear
Fig. 13
11.1
Functions
ƒ
Automated starting and stopping of the electric pump
ƒ
Operation in twin groups with alternation
ƒ
Easy and precise adjustment of the working pressures by means of the display
ƒ
Dry-running protection with automatic reset
ƒ
Can be installed in both horizontal and vertical position
ƒ
Digital indication of pressure and current consumption on the display
ƒ
LED indicating operating status (network, error, pump running)
ƒ
Digital input for float switch or remote control connection