Switchgear of diesel pump
60
WILO SE 2020-12
M10 – Motor temperature 2
Unit
Standard
Area
P10.07
MIN Alarm limit temperature
°
OFF
OFF/ 20-300
P10.08
Heater activation threshold
°
OFF
OFF/ 20-300
P10.09
Heater deactivation threshold
°
OFF
OFF/ 20-300
P10.10
Faulty temperature sensor alarm delay
Min.
OFF
OFF/1–60
M11 – Fuel level
Unit
Standard
Area
P11.01
Source measure.
Specifies from which source the fuel level meas-
urement is taken. OFF= not managed. RES3 =
taken from the resistive sensor with analogue in-
put on terminal RES3. AINx = taken from the ana-
logue input of an EXP expansion module. RES
AN= taken from the resistive input of an EXP ex-
pansion module.
OFF
OFF
RES3
AINx
RES AN
P11.02
Channel number.
Channel number (x) to be specified if AINx has
been selected in the previous parameter.
1
1 … 4
P11.03
Resistive sensor type.
If a resistive sensor is used, select which curve to
use. Characteristic curves can be set freely using
the Xpress software.
VDO
VDO / DATCON / VEGLIA /
MURPHY
P11.04
Resistive sensor offset.
If a resistive sensor is used, it allows to add or re-
move an offset in Ohm to the set the curve to
compensate, for example, the cable length. This
value can also be set without entering setup us-
ing the quick function in the command menu
which allows you to see the measurements while
performing calibration.
Ohm
0
-30.0 … +30.0
P11.05
Capacity unit of measurement
%
% / l /gal
P11.06
Tank capacity
OFF
OFF / 1-30000
P11.07
Rated hourly motor consumption
(P11.05)/h
OFF
OFF / 0.0-200.0
P11.08
MIN Pre-alarm fuel
%
OFF
OFF / 1-100
P11.09
MIN Fuel level
%
66
OFF / 1-100
P11.10
Start level fuel topping up pump
%
OFF
OFF / 1-100
P11.11
Fuel filler pump stop level
%
OFF
OFF / 1-100
P11.12
MAX Pre-alarm fuel
%
90
OFF / 1-100
P11.13
MAX fuel level alarm
%
95
OFF / 1-100
M12 – Motor start
Unit
Standard
Area
P12.01
Battery charger alternator voltage threshold
With the motor running and the voltage below
the set threshold, the A42 battery charger altern-
ator failure alarm is generated. In the event of ab-
sence of the signal W there is the recognition
threshold of the motor in motion by the battery
charger alternator voltage (D+/AC).
VDC
10.0
OFF/3.0-30
P12.02
Threshold started by motor speed.
Threshold recognition of motor running by speed
signal 'W' or pick-up
%
30
OFF/10-100
P12.03
Glow plugs preheating time
S
OFF
OFF/1-60
P12.04
Number of start-up attempts
S
6
1-30
P12.05
Start attempt duration
S
8
1-60
P12.06
Pause between start-up attempts
S
8
1-60