Switchgear of diesel pump
en
Installation and operating instructions Wilo-SiFire FIRST
67
CODE
DESCRIPTION
CAUSE
A72
Jockey pump starts alarm
Alarm generated when the threshold set in parameter
P02.19 is exceeded if there is an input programmed with
the - Pilot pump function.
A73
Thermal alarm jockey pump
Alarm generated by the input programmed with the
function - Thermal pilot pump.
A74
Drainage pump alarm
Alarm generated by the input programmed with the
function - Drain pump fault.
A75
Fuel liquid leakage
Alarm generated by the input programmed with the
function - Fuel leakage alarm.
A76
Communication error
When parameter P17.n.9 is set as main pump+1 or main
pump+2 and the device is not able to communicate with
1 or 2 devices.
A77
Jockey pump timeout
Alarm generated when the threshold set in parameter
P02.20 is exceeded if there is an input programmed with
the function - Pilot pump in operation.
A78
Open test valve
Alarm generated by the input programmed with the
function - Test valve.
UA1
User alarm 1
The user alarm is generated by activation of the variable
or the associated input via the M24 menu.
…
…
UA8
User alarm 8
10.5
Overview of functions
10.5.1
Overview of input functions
The following table shows all the functions that can be associated with INPn program-
mable digital inputs. Each input can then be set so as to have an inverted function (NO/
NC), to be delayed when energised or de-energised with independent settable times.
Some functions require an additional numerical parameter, defined with the index (x)
specified by parameter P15.n.02. See menu M15 Programmable Inputs for more details.
Function
Description
Disabled
Input disabled.
Configurable
Free user configuration. To be used, for example, if the input is used in a PLC logic.
Start pressure switch
Motor pump starting from pressure switch contacts.
Start from priming tank level
Priming level sensor for start.
Automatic start lock
Automatic mode exclusion selector.
Oil pressure
Digital motor oil low pressure sensor.
Low motor temperature
Digital minimum motor temperature sensor (heater failure).
High motor temperature
Maximum motor temperature digital sensor.
Fuel level
Low fuel level digital sensor.
Water reserve
Water reserve alarm.
External automatic test
Starts the periodic test managed by an external timer.
Remote control lock
Locks command and write operations via serial port. Data reading is always possible.
Lock set-up
Inhibits access to the programming menu.
Keypad lock
Locks the operation of the front keyboard, excluding page navigation keys.
Radiator liquid level
When the input is activated, a low radiator liquid alarm is generated.
Siren OFF
Disables the siren.
Battery charger alarm A
With input activated, it signals battery charger A failure alarm. The alarm is generated only with
mains voltage present.
Battery charger alarm B
With input activated, it signals battery charger B failure alarm. The alarm is generated only with
mains voltage present.
Alarm inhibition
If activated, it allows to disable the alarms with the property "Alarm Inhibition" activated
Reset alarms
Reset of the alarm whose triggering condition has ceased
Command menu Cxx
Executes the command menu command defined by the index parameter (x).
Simulate STOP key
Closing the input is equivalent to pressing the STOP key.