Switchgear of diesel pump
en
Installation and operating instructions Wilo-SiFire FIRST
49
CODE
COMMAND
ACCESS
DESCRIPTION
C06
Reset LIMx limits status
User
Resets the status of the retention LIMx limits.
C07
Total engine hour counter reset
Advanced
Resets the total hours counter of the electropump.
C08
Motor hour meter setting
Advanced
It allows to set the total hours counter of the electric pump
to a desired value.
C09
Startup counter reset
Advanced
Resets the start attempt counter and the percentage of
successful attempts
C10
Reset MAX/MIN
Advanced
Resets the maximum and minimum values.
C11
Reset event list
Advanced
Resets the list of events history.
C12
Reset parameters to default
Advanced
Resets all set-up menu parameters to factory setting
C13
Save parameters to backup
memory
Advanced
Copies the currently set parameters to a backup area for
future restoration.
C14
Reload parameters from backup
memory
Advanced
Transfers the parameters saved in the backup memory to
the active settings memory.
C15
I/O Forcing
Advanced
Enables the test mode that allows you to manually energise
any output.
NOTICE:
In this mode, the responsibility for controlling the out-
puts is completely entrusted to the end-user.
C16
PLC program reset
Advanced
Clears the program with PLC logic from the internal
memory
Once you have selected the desired command, press
to execute it. The instru-
ment will ask for confirmation. Pressing again
the command will be executed.
To cancel the execution of a selected command press STOP. To exit the command
menu press STOP.
10
Switchgear of diesel pump
Fig. 12
Description
FN2
EMC filter
FU2
Fuses
GD1
Battery charger - Battery 1
GD2
Battery charger - Battery 2
HMI
Human Machine Interface
KA1-4
Auxiliary relays
KM1-2
Battery power contactor
KT1
Amperometric transformer
M1, M2
Clamps
MC
Fuse clamps
QS1
Main switch
SA1
Auto mode key switch
SB1
Manual emergency start button - Battery 1
SB2
Manual emergency start button - Battery 2
VC1
Diode bridge
10.1
Functions
10.1.1
Main screen
Fig. 12.2
Description