M
easured value on the indicating and adjustment module does not
correspond to the value in the
PLC
l
T
he menu item
"
D
isplay
-
D
isplay value
"
is not set to
"
PA
-
O
ut
"
à
C
heck values and correct
,
if necessary
?
N
o connection between
PLC
and
PA
network
l
I
ncorrect adjustment of the bus parameter and the segment
coupler
-
dependent baud rate
à
C
heck data and correct
,
if necessary
?
I
nstrument does not appear during connection setup
l
P
ro
fi
bus
DP
cable pole
-
reversed
à
C
heck cable and correct
,
if necessary
l
I
ncorrect termination
à
C
heck termination at the beginning and end points of the bus
and terminate
,
if necessary
,
according to the speci
fi
cation
l
I
nstrument not connected to the segment
,
double assignment
of an address
à
C
heck and correct
,
if necessary
I
n
E
x applications
,
the regulations for the wiring of intrinsically safe
circuits must be observed
.
?
E
013
l
no measured value available
9
)
à
E
xchange instrument or return instrument for repair
?
E
017
l
A
djustment span too small
à
repeat with modi
fi
ed values
?
E
036
l
no operable sensor software
à
C
arry out a software update or send the instrument for repair
?
E
041
l
H
ardware error
,
electronics defective
à
E
xchange instrument or return instrument for repair
?
E
113
l
C
ommunication con
fl
ict
à
E
xchange instrument or return instrument for repair
9
)
F
ault message can also appear if the pressure is higher than the nominal
range
.
F
ault messages via the
indicating
/
adjustment
module
P
rocess pressure transmitter
IPT
-
11
V
ers
.
4
.
0
-
ceramic sensor
•
P
ro
fi
bus
PA
37
8
M
aintenance and fault recti
fi
cation
31547
-
EN
-
081211