I
n the menu items
"
zero
"
and
"
span
"
you determine the span of the
sensor
,
the span corresponds to the end value
.
I
nformation
:
T
he steps
1
,
3
and
4
are not necessary for instruments which are
already preset according to customer speci
fi
cations
!
Y
ou can
fi
nd the data on the type label on the instrument or in the
menu items of the zero
/
span adjustment
.
T
he indicating and adjustment module enables the adjustmetn without
fi
lling or pressure
.
T
hanks to this
,
you can carry out your settings
already in the factory without the instrument having to be installed
.
T
he actual measured value is displayed in addition to the menu items
for zero
/
span adjustment
.
IPT
-
1
*
V
ers
.
4
.
0
is preset to application
"
L
evel measurement
"
.
P
roceed as follows when switching over to application
"
P
rocess
pressure measurement
"
:
1
P
ush the
[
OK
]
button in the measured value display
,
the menu
overview is displayed
.
2
S
elect the menu
"
S
ervice
"
with
[-
>
]
and con
fi
rm with
[
OK
]
.
B
asic adjustment
D
isplay
D
iagnostics
▶
S
ervice
I
nfo
3
S
elect the menu item
"
A
pplication
"
with
[-
>
]
and edit with
[
OK
]
.
W
arning
:
N
ote the warning
:
"
O
utput can change
"
.
4
S
elect with
[-
>
]
"
OK
"
and con
fi
rm with
[
OK
]
.
5
S
elect
"
P
rocess pressure
"
from the list and con
fi
rm with
[
OK
]
.
I
n this menu item you select the adjustment unit as well as the unit for
the temperature indication in the display
.
T
o select the adjustment unit
(
in the example switching over from bar
to mbar
)
you have to proceed as follows
:
5
)
1
P
ush the
[
OK
]
button in the measured value display
,
the menu
overview is displayed
.
5
)
S
election options
:
mbar
,
bar
,
psi
,
P
a
,
k
P
a
,
MP
a
,
in
H
g
,
mm
H
g
,
in
H
2
O
,
mm
H
2
O
.
S
elect application
"
P
rocess pressure
measurement
"
S
elect unit
P
rocess pressure transmitter
IPT
-
11
V
ers
.
4
.
0
-
ceramic sensor
•
P
ro
fi
bus
PA
27
6
S
et up with the indicating and adjustment module