WIKA Operating Instructions - Differential pressure transmitter DPT-10
– bar, PSI, …, m, ft, …; in case of length type engineering unit and access to parameters the cor-
responding values will be converted by density factor
•
secondary_value_2
– Value after min/max-adjustment. Selected as input to AIFB by setting 'Channel' = 3. Unit
derives from 'Secondary_value_2_unit'
•
secondary_value_2_unit
– Selected unit code for "secondary_value_2"
•
sensor_value
– Raw sensor value, i.e. the uncalibrated measurement value from the sensor. Unit derives from
'Sensor_range.unit'
•
sensor_range
– "Sensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'
– includes sensor unit: bar, PSI …; only unit part of DS-68 is writable
•
simulate_primary_value
•
simulate_secondary_value_1
•
simulate_secondary_value_2
•
device status
– "0: ""OK""
– 13: ""non-specific error""
– 17: ""Cal span too small""
– 34: ""EEPROM memory fault""
– 36: ""ROM memory fault""
– 37: ""RAM memory fault""
– 40: ""non-specific hardware fault""
– 41: ""Sensor element not found""
– 42: ""No leaking pulse""
– 43: ""No trigger signal""
– 44: ""EMI error""
– 113: ""Communication hardware fault"""
•
linearization type
– Possible types of linearization are: linear, user defined, cylindrical lying container, spherical
container
– "0: ""Linear""
– 1: ""User def""
– 20: ""Cylindrical lying container""
– 21: ""Spherical container"""
•
curve_points_1_10
– X and Y values for the user defined linearization curve
•
curve_points_11_20
– X and Y values for the user defined linearization curve
•
curve_points_21_30
– X and Y values for the user defined linearization curve
•
curve_points_31_33
– X and Y values for the user defined linearization curve
•
curve status
– Result of table plausibility check
– "0: ""Uninitialized""
– 1: ""Good""
– 2: ""Not monotonous increasing""
– 3: ""Not monotonous decreasing""
– 4: ""Not enough values transmitted""
– 5: ""Too many values transmitted""
– 6: ""Gradient of edge too high""