41
6 Adjustment with the display and adjustment module
WIKA Operating Instructions - Differential pressure transmitter DPT-10
Information:
The applications density and interface measurement are also realized
via the application level measurement.
Proceed as follows to switch over to the application differential pres-
sure or flow measurement:
1. Push the
[OK]
button in the measured value display, the menu
overview is displayed.
▶
Basic adjustment
Display
Diagnostics
Service
Info
2. Confirm the menu "
Basic adjustment
" with
[OK]
.
Application
Level
▼
3. Confirm the menu item "
Application
" with
[OK]
.
Warning:
Note the warning: "
Output can change
".
4. Select with
[->]
"
OK
" and confirm with
[OK]
.
5. Select the requested application in the selection list, for example
"
Flow
" and confirm with
[OK]
.
In this menu item you select the adjustment unit as well as the unit for
the temperature indication in the display.
To select the adjustment unit (in the example switching over from
mbar to bar), proceed as follows:
1. Push the
[OK]
button in the measured value display, the menu
overview is displayed.
▶
Basic adjustment
Display
Diagnostics
Service
Info
2. Confirm the menu "
Basic adjustment
" with
[OK]
, the menu item
"
Unit
" will be displayed.
Unit
Unit of measurement
mbar
▼
Temperature unit
°C
▼
3. Activate the selection with
[OK]
and select "
Units of measure-
ment
with
[->]
.
4. Activate the selection with
[OK]
and select the requested unit with
[->]
(in the example bar).
5. Confirm with
[OK]
and move to position correction with
[->]
.
Basic adjustment - Unit