6 Commissioning, operation
22 WIKA Operating Instruction, Pascal ET, ET-P, ET/IS, ET-P/IS
GB
The module allow the 24V to supply directly the output loop for the transmitter.
Further, it can supply a 250Ω load resistance electronically switchable necessary to HART
communication, permitting to avoid the use of an external one.
The following figure shows the pin connections in HART module:
Figure 3
– HART module
6.1.2.4.1 HART wiring
Depending by several factors and combination that the user can found in a plant, there are many
wiring possibility depending by:
Using module internal or external Power Supply.
Using internal or external load resistance.
Simultaneous analog connection of AO TRX to one Input module for mA reading
Please consider, if the user enable the internal load resistance, this will be connected between the
+HART and COM terminals.
Here same examples:
Figure 4 -
Case 1: 24V from module, 250Ω from module
Transmitter
HART slave