 INSTALLATION

yes

yes

yes

no

no

no

no

no

no

no

no

yes

yes

yes

yes

Reset control to clear lockout and confirm fault.

Rapid Flash = Flame Sensed when no flame should be present. 

1 Flash = Number of Retries exceeded, control locked out.

2 Flashes = Recycles Exceeded, control locked out.

Red Light continuous indicates either an internal fault or 

miswired gas valve. Check wires at MV1 and MV2 for proper 

connection or swap wires to correct fault. If fault persists, 

replace module.

Call for heat, Thermostat 

contacts close

Does Yellow LED light for 

approximately 2 seconds? 

(Module Self Check)

Does Yellow LED Flash? 

Does Red LED Flash or remain

lit?

Check Low Voltage to module (TH-TR). If no voltage:

Check Limit Switches

Check vent pressure switch (if used).

Measure AC voltage between terminal L1 and TH. If voltage 

is approximately 145 VAC, polarity is reversed; reverse 

secondary leads on control transformer. Correct reading 

should be approximately 95 VAC.

Check Low Voltage  to module (TH-TR).

Check Limit Switches

Check vent pressure switch (if used).

Indicates a poor flame sense signal. Check for short in Flame 

Sensor wiring, Poor  Furnace or Burner Ground, Shorting 

flame sensor, flame sensor wiring, or dirty flame probe.

Clean flame probe.

Confirm 120 Volts to ignitor terminals (HS1 and L2 on 

module) If voltage is present replace ignitor.

Check gas supply and pressure to valve.

Check for 24 volt output on module (terminals MV1 and MV2). 

If no voltage replace module. 

If gas valve is receiving voltage but not opening replace valve. 

Check limit switches.

Check sensor lead and ground for continuity.

Check insulator of flame sensor  or ignitor for excessive 

temperature. Temperature above 1000 deg F. can ground 

flame sense.

Does system run until call for 

heat ends?

Does the main burner light?

After prepurge does ignitor 

glow red?

Does Green LED Flash?

Does Green LED Light?

Yes

Normal Operation

Summary of Contents for 50E47-843

Page 1: ...dule diagnostics and troubleshooting GENERAL PRECAUTION Do not use on circuits exceeding specified voltage Higher voltage will damage control and could cause shock or fire hazard Do not short out term...

Page 2: ...fer to the wiring diagrams and wiring table when connect ing the control to other components of the system UL approved 105 C rated 18 gauge minimum wire is recom mended for all low voltage connections...

Page 3: ...RANSFORMER JUMPER M V 2 T R G N D T H M V 1 L 2 F P L 1 H S 1 THERMOSTAT OR CONTROLLER ALTERNATE LIMIT L1 HOT L2 LIMIT CONTROLLER FLAME PROBE RED ADAPTER BLUE HOT SURFACE IGNITER MV MV GAS VALVE BURNE...

Page 4: ...ain open until the call for heat is satisfied During the trial for ignition period the ignitor is turned off If the burner does not light the control will either go into lockout or make two more ignit...

Page 5: ...is reversed reverse secondary leads on control transformer Correct reading should be approximately 95 VAC Check Low Voltage to module TH TR Check Limit Switches Check vent pressure switch if used Indi...

Page 6: ...St Louis Missouri White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co www white rodgers com www emersonclimate com...

Page 7: ...ptor de presi n de venteo si se utiliza Indica una se al de detecci n de llama d bil Verifique que no haya un cortocircuito en las conexiones del detector de llama una mala conexi n a tierra de la cal...

Page 8: ...tes externos o en las conexiones vea el siguiente cuadro Proceda como se indica a continuaci n Tres verificaciones visuales 1 El dispositivo de encendido se calienta y se ilumina de color rojo 2 La ll...

Page 9: ...e de que quede la tecla correcta en el m dulo La inversi n de los cables de la v lvula de gas o una conexi n abierta a MV1 y MV2 pueden hacer que el control se bloquee Vea c mo proceder en la gu a de...

Page 10: ...ecci n indirecta usando una sonda de llama Fig 3 Conexi n t pica para el repuesto de la competencia con detecci n de llama indirecta a trav s de una sonda de llama a Retire la conexi n r pida y c mbie...

Page 11: ...ede montarse sobre una caja de conexiones de 4 pulg x 4 pulg usando dos tornillos mec nicos calibre 8 32 x 5 8 pulg El control debe fijarse en un lugar que est sujeto a un m nimo de vibraciones y que...

Page 12: ...om www emersonclimate com Para evitar descargas el ctricas y o da os al equi po desconecte la alimentaci n el ctrica en la caja de fusibles o disyuntores principal hasta que haya finalizado la instala...

Reviews: