INSTALLATION 

INSTALL PROGRAM KEY

The control replaces all listed models with the following 
features:

•  120 volt hot surface ignitor
•  remote rod flame sense or direct flame sense through ignitor
•  one or three ignition tries
•  Seven or four second trial for ignition intervals
•  Pre-purge of 30 seconds or less
•  60 second inter-purge time
•  17 or 45 second ignitor warm-up times

Six program keys are provided for different applications. 
Timings and Retries for each program key are shown in the 

Specifications section of this installation manual. Choose the 

proper program key for the application by using the Module 
Cross Reference (37-7209). Install the selected program key in 

the slot on the left side of the module (see figure 4 on page 3).
If the module you are replacing is not listed in the Cross 
Reference, contact the manufacturer of the appliance for a 
recommended replacement or retrofit.

After inserting the proper program key, dispose of the 
remaining keys to ensure the correct key remains in the 

module.
Reversal of gas valve leads or open connection to MV1 and 

MV2 may cause control to lockout. See troubleshooting guide 

for remedy.

OPERATION 

TROUBLESHOOTING 

TYPICAL FURNACE INSTALLATION

In a typical application the 50E47-843 is designed to energize 

the ignitor and gas valve and monitor the flame sensor. It 

is a 100% shut off design that locks out the gas valve if the 

burner does not light within the trial for ignition period. The 

ignition sequence begins with a call for heat from the room 

thermostat. The thermostat applies power to the control. 

After pre-purge interval, the ignitor warms up for the selected 
time. The control energizes the gas valve for the selected 

trial for ignition period. If the burner lights within the allowed 
period the gas valve will remain open until the call for heat 
is satisfied. During the trial for ignition period the ignitor is 
turned off. If the burner does not light, the control will either 

go into lockout or make two more ignition retries depending 
on the options selected. The control can be reset from lockout 

by cycling the thermostat to remove power for a minimum of 

3 seconds. It includes a system analysis/troubleshooting LED 
that indicates normal operation, lockout, weak flame signal or 

internal control fault.

For proper control operation, the control must be electrically 
connected to the gas valve and all the ignitor wiring connec-

tors plugged in. Gas valves with an electric "ON/OFF" switch 

must have the switch set to "ON".
The light on the control provides a self-diagnosis indication. 
If the red light on the module is on continuously, the fault is 

likely to be internal to the module. To make sure, interrupt 

the line or 24 volt thermostat power for a few seconds and 
then restore. If the internal fault is indicated again, and flame 

sensor is not shorted to ground, replace the control. A flash

-

ing light indicates the problem is most likely in the external 

components or wiring (see chart below). Proceed as follows:

Three visual checks

1.  The ignitor will warm up and glow red
2.  The main burner flame will ignite
3.  The main burner flame will continue to burn after the 

ignitor is turned off

Troubleshooting the system consists of checking for these 

three visual indications. The chart on the next page defines 
the proper action if any of these indications do not occur.

LED

Condition

Green

Solid On

Normal

Green

Rapid Flashing

Weak flame signal

Red

Rapid Flash

Control in lockout

Flame sensed when

there should be none

Red

1 Flash

Control in lockout

Ignition retries exceeded

Red

2 Flash

Control in lockout

 

Ignition recycles exceeded

Yellow

Solid On

Internal self check

Yellow

Rapid Flashing

Improper Polarity

OFF

Internal Failure

Red

Solid On

Gas valve miswired or

Internal error detected

Summary of Contents for 50E47-843

Page 1: ...dule diagnostics and troubleshooting GENERAL PRECAUTION Do not use on circuits exceeding specified voltage Higher voltage will damage control and could cause shock or fire hazard Do not short out term...

Page 2: ...fer to the wiring diagrams and wiring table when connect ing the control to other components of the system UL approved 105 C rated 18 gauge minimum wire is recom mended for all low voltage connections...

Page 3: ...RANSFORMER JUMPER M V 2 T R G N D T H M V 1 L 2 F P L 1 H S 1 THERMOSTAT OR CONTROLLER ALTERNATE LIMIT L1 HOT L2 LIMIT CONTROLLER FLAME PROBE RED ADAPTER BLUE HOT SURFACE IGNITER MV MV GAS VALVE BURNE...

Page 4: ...ain open until the call for heat is satisfied During the trial for ignition period the ignitor is turned off If the burner does not light the control will either go into lockout or make two more ignit...

Page 5: ...is reversed reverse secondary leads on control transformer Correct reading should be approximately 95 VAC Check Low Voltage to module TH TR Check Limit Switches Check vent pressure switch if used Indi...

Page 6: ...St Louis Missouri White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co www white rodgers com www emersonclimate com...

Page 7: ...ptor de presi n de venteo si se utiliza Indica una se al de detecci n de llama d bil Verifique que no haya un cortocircuito en las conexiones del detector de llama una mala conexi n a tierra de la cal...

Page 8: ...tes externos o en las conexiones vea el siguiente cuadro Proceda como se indica a continuaci n Tres verificaciones visuales 1 El dispositivo de encendido se calienta y se ilumina de color rojo 2 La ll...

Page 9: ...e de que quede la tecla correcta en el m dulo La inversi n de los cables de la v lvula de gas o una conexi n abierta a MV1 y MV2 pueden hacer que el control se bloquee Vea c mo proceder en la gu a de...

Page 10: ...ecci n indirecta usando una sonda de llama Fig 3 Conexi n t pica para el repuesto de la competencia con detecci n de llama indirecta a trav s de una sonda de llama a Retire la conexi n r pida y c mbie...

Page 11: ...ede montarse sobre una caja de conexiones de 4 pulg x 4 pulg usando dos tornillos mec nicos calibre 8 32 x 5 8 pulg El control debe fijarse en un lugar que est sujeto a un m nimo de vibraciones y que...

Page 12: ...om www emersonclimate com Para evitar descargas el ctricas y o da os al equi po desconecte la alimentaci n el ctrica en la caja de fusibles o disyuntores principal hasta que haya finalizado la instala...

Reviews: