TROUBLESHOOTING GUIDE
PROBLEMS OR
SYMPTOMS
CAUSES
TROUBLESHOOTING
Unit does not
work
1. - Power supply problem.
1. - Main Switch shut down (Off).
Switches and/or or actuated external fuses.
Loose cables and/or terminals.
Missing phase or bad neutral wiring, or two equal
phases.
2. - Room temperature lower than set-
point adjustment of Controller.
2 Add charge to the room or wait until room temperature
increases
3. - Shut down due to low pressure
switch.
3. - Check for cooling gas leaks.
Change clogged air filters
Check evaporator motor: burnt or locked.
4. - Shut down due to high pressure
switch
4. - Condenser motor locked or burnt.
Dirty condenser coil or with lumps
Excess gas, added in previous repair.
5. - Electrical wiring error
5. - Check electric wiring of assembly again
6. - No supply voltage reaches the
Controller
6. - Transformer is burnt or if DC to controller, key
switched off.
System
operates
continuou
sly and
insufficie
ntly.
1. - The unit is not enough to cool the
room.
1. - Make a heat balance, determine capacity to be
added.
2.- Damaged component malfunction.
2. - Replace damaged switches, adjust loose blowers,
clean dirty coils.
3 - Gas leaks
3. - Repair gas leaks, install and/or adjust service valve
caps and nuts. Charge additional gas.
4. - Defective compressor
4. - Replace compressor.
5. - Clogged air filter, low performance
(lack of air)
5. - Replace air filter.
Thermal
relays
of contactors
are actuated
1.
-
Inappropriate wiring for power
consumption
1. - Replace cable section.
2. - Defective motors and/or compressors
3.- Replace them
3.-Low voltage (10% lower than nominal
voltage)
4. - Manage troubleshooting.
Water inside
unit.
1. Drain pipe clogged and overflowing
into drain pan.
1.- Clean drain pipe.
Failure outputs are two relays which are always connected (on). Upon a failure, they change their status. If the PLC is
switched off, they also change their status because they are disconnected (off).
"
Not Urgent
" output is switched off with any failure.
"
Urgent
" output is switched off when two or more units have an alarm.
.
Summary of Contents for IW Series
Page 1: ......
Page 2: ...76 5276 05 Page 2 of 82 ...
Page 4: ...76 5276 05 Page 4 of 82 ...
Page 6: ...76 5276 05 Page 6 of 82 ...
Page 11: ...76 5276 05 Page 11 of 82 Different air flow configuration ...
Page 12: ...76 5276 05 Page 12 of 82 IW 005 006 Side Air Flow Rear Air Return Indoor Unit Dimensions ...
Page 13: ...76 5276 05 Page 13 of 82 IW 005 006 Front Air Flow Rear Air Return Indoor Unit Dimensions ...
Page 14: ...76 5276 05 Page 14 of 82 IW 005 Outdoor Unit Dimensions ...
Page 15: ...76 5276 05 Page 15 of 82 IW 006 Outdoor Unit Dimensions ...
Page 24: ...76 5276 05 Page 24 of 82 Slideable Electrical Panel View ...
Page 27: ...76 5276 05 Page 27 of 82 Installation and Assembly ...
Page 60: ...76 5276 05 Page 60 of 82 Settings for Gmail ...
Page 61: ...76 5276 05 Page 61 of 82 ...
Page 69: ...76 5276 05 Page 69 of 82 ...
Page 73: ...76 5276 05 Page 73 of 82 Drain Pump Optional ...
Page 75: ...76 5276 05 Page 75 of 82 PLC Electrical connection diagram with remote display ...
Page 76: ...76 5276 05 Page 76 of 82 IW 005 006 Control Electrical Diagram ...
Page 77: ...76 5276 05 Page 77 of 82 IW 005 Power Electrical Diagram ...
Page 78: ...76 5276 05 Page 78 of 82 IW 006 Power Electrical Diagram ...
Page 82: ...76 5276 05 Page 82 of 82 ...