Setpoint with input sensors
In this screen the programmed values (setpoints) are displayed for each function. It must be taken into account that for
cooling, it must be adjusted according to the selected sensors: If the input sensors have been selected, a setpoint
between 30 and 33ºC is recommended, while if the output ones are selected, a setpoint between 20 and 23ºC is
recommended
Temperature and Humidity
Alarms delay
0 seconds
In this screen the programmed time delay value of the temperature and humidity alarms is displayed.
If there is a temperature or humidity alarm, it will only appear if the amount of time programmed in this instance is in that
state, if the time is zero the alarm will be immediate
Temperature Alarm
High 35.0 ° C
Low 10.0 ° C
In this screen, the programmed values for the temperature alarm are displayed. If the temperature exceeds any of these
values, the unit will fail. It must be taken into account if the input or output sensors were selected, since the alarms will be
different for both cases.
The reset of this alarm is automatic, when the ambient humidity value is within the programmed range.
Humidity Alarm
High
85.0%
Low
25.0%
In this screen, the programmed values for the humidity alarm are displayed, if the humidity exceeds any of these values,
the unit will fail.
The reset of this alarm is automatic, when the ambient humidity value is within the programmed range.
Low pressure switch
Retry: Yes
Time between
Retries 5 Min.
In this screen, you can see if you have and the number of retries to re-start the unit again in case of a low-pressure alarm
(Low pressure switch).
It is displayed if the retry function is activated, and the time it takes the unit to retry starting.
Low pressure switch
Amount of retries
3 times
Current retries
0
Total time
60Min
In this screen, more values are displayed for the low-pressure alarm. The first is the number of times the controller retries
the start of the unit after an alarm by low pressure switch. Once this amount is reached, the unit will not retry, being
stopped by failure. "Current retries" indicates at the moment, how many restart attempts the unit has made due to an
alarm by low pressure switch. The "Total Time" indicates the time in which the retries will be counted, elapsed since the
first failure. That is, if the maximum number of retries allowed has not been reached, after this time, the counter returns to
0.
Summary of Contents for IW Series
Page 1: ......
Page 2: ...76 5276 05 Page 2 of 82 ...
Page 4: ...76 5276 05 Page 4 of 82 ...
Page 6: ...76 5276 05 Page 6 of 82 ...
Page 11: ...76 5276 05 Page 11 of 82 Different air flow configuration ...
Page 12: ...76 5276 05 Page 12 of 82 IW 005 006 Side Air Flow Rear Air Return Indoor Unit Dimensions ...
Page 13: ...76 5276 05 Page 13 of 82 IW 005 006 Front Air Flow Rear Air Return Indoor Unit Dimensions ...
Page 14: ...76 5276 05 Page 14 of 82 IW 005 Outdoor Unit Dimensions ...
Page 15: ...76 5276 05 Page 15 of 82 IW 006 Outdoor Unit Dimensions ...
Page 24: ...76 5276 05 Page 24 of 82 Slideable Electrical Panel View ...
Page 27: ...76 5276 05 Page 27 of 82 Installation and Assembly ...
Page 60: ...76 5276 05 Page 60 of 82 Settings for Gmail ...
Page 61: ...76 5276 05 Page 61 of 82 ...
Page 69: ...76 5276 05 Page 69 of 82 ...
Page 73: ...76 5276 05 Page 73 of 82 Drain Pump Optional ...
Page 75: ...76 5276 05 Page 75 of 82 PLC Electrical connection diagram with remote display ...
Page 76: ...76 5276 05 Page 76 of 82 IW 005 006 Control Electrical Diagram ...
Page 77: ...76 5276 05 Page 77 of 82 IW 005 Power Electrical Diagram ...
Page 78: ...76 5276 05 Page 78 of 82 IW 006 Power Electrical Diagram ...
Page 82: ...76 5276 05 Page 82 of 82 ...