76-5276-05
Page 72 of 82
7 slow flashes
External control
signal not
connected correctly
(2-10V only); or - for
control via serial
(variable I62 bit2=1)
- no data over 485
serial connection
(cable probably
disconnected).
Cable broken/
disconnected/
not connected
correctly.
Check and connect
correctly.
ESC
yes
humidif.
stopped
Incorrect voltage
of external control
signal.
Set A0 =1; based on
external signal
set A2 = 0: 0-1V, A2=1
0-10V, A2=2 2-10V, A2=3
0-20mA, A2=4 4-20mA
8 slow flashes
High water
level without
humidification
demand. Alarm
ON if the water
reaches the high
level electrodes
when the humidifier
is shutdown or
disabled (contactor
open, fill & drain
valves closed)
Leaks from the fill
valve.
Check for any leaks from
the fill valve and clean/
replace
AUTO
yes
humidif.
stopped
High level sensor
short-circuited.
If possible, open the
cylinder and clean it.
Malfunction of the
high level sensor
electrical circuit .
Make sure the electrical
connections between
the sensor and the board
are correct: reconnect if
necessary or replace the
board.
Red LED on
board (if terminal
not connected)
(*)
description
cause
solution
reset
(press)
alarm relay
activation
action
9 slow flashes
Foam
Lubricants, solvents,
detergents in the
supply water (at
times the water
hoses are dirty after
installation).
Wash all water supply
hoses thoroughly. The
water conductivity must
be between 75 and1250
μS/cm. Softening the
water may worsen the
problem.
ESC
no
signal
only
Softened water.
High level sensor
short-circuited.
If possible, open the
cylinder and clean it.
Malfunction of the
high level sensor
electrical circuit.
Make sure the electrical
connections between
the sensor and the board
are correct; if necessary
replace the board
10 slow flashes
Cylinder depleted.
The alarm is
displayed when the
cylinder is almost
depleted - and
production cannot
satisfy demand
within 3 hours from
the cylinder almost
depleted warning.
The “Cylinder almost
depleted” and
“Cylinder depleted”
warnings can be
disabled by b1-
parameter.
The cylinder is full
of flakes.
Replace the cylinder
--
no
signal
only
none
Cylinder cleaning
phase started
signal
--
--
--
none
Cylinder drain in
progress
--
--
--
(both codes
displayed
alternating)
Complete drain
due to
inactivity
--
--
none
Antifoam active
--
--
--
To reset the alarms, press ESC once to mute the buzzer, press ESC a second time to reset the alarm itself.
Fast flash: 0.2 seconds ON and 0.2 seconds OFF
Para resetear las alarmas, presionar ESC, una vez silenciado el sonido, presionar ESC nuevamente.
Pulsos rápidos: Leds On/Off en intervalos de 0,2 segundos.
Pulsos lentos: Leds On/Off en intervalos de 1 segundo.
Summary of Contents for IW Series
Page 1: ......
Page 2: ...76 5276 05 Page 2 of 82 ...
Page 4: ...76 5276 05 Page 4 of 82 ...
Page 6: ...76 5276 05 Page 6 of 82 ...
Page 11: ...76 5276 05 Page 11 of 82 Different air flow configuration ...
Page 12: ...76 5276 05 Page 12 of 82 IW 005 006 Side Air Flow Rear Air Return Indoor Unit Dimensions ...
Page 13: ...76 5276 05 Page 13 of 82 IW 005 006 Front Air Flow Rear Air Return Indoor Unit Dimensions ...
Page 14: ...76 5276 05 Page 14 of 82 IW 005 Outdoor Unit Dimensions ...
Page 15: ...76 5276 05 Page 15 of 82 IW 006 Outdoor Unit Dimensions ...
Page 24: ...76 5276 05 Page 24 of 82 Slideable Electrical Panel View ...
Page 27: ...76 5276 05 Page 27 of 82 Installation and Assembly ...
Page 60: ...76 5276 05 Page 60 of 82 Settings for Gmail ...
Page 61: ...76 5276 05 Page 61 of 82 ...
Page 69: ...76 5276 05 Page 69 of 82 ...
Page 73: ...76 5276 05 Page 73 of 82 Drain Pump Optional ...
Page 75: ...76 5276 05 Page 75 of 82 PLC Electrical connection diagram with remote display ...
Page 76: ...76 5276 05 Page 76 of 82 IW 005 006 Control Electrical Diagram ...
Page 77: ...76 5276 05 Page 77 of 82 IW 005 Power Electrical Diagram ...
Page 78: ...76 5276 05 Page 78 of 82 IW 006 Power Electrical Diagram ...
Page 82: ...76 5276 05 Page 82 of 82 ...