76-5276-05
Page 70 of 82
Humidifier Troubleshooting
Red LED
on board
description
cause
solution
reset
(press)
alarm
relay
activation
action
2 fast flashes
Excess electrode
current: current>
maximum limits
Conductivity of
the water too high,
errata configuration
TAM
The water conductivity must
be between 75 and1250
μS/cm. Softening the water
may worsen the problem
AUTO
yes
humidif.
stopped
TAM electrical
circuit not
configured
correctly
Switch unit off and
configure TAM jumper.
Switch unit on and check if
the alarm is repeated.
Malfunction in
the TAM electrical
circuit
Check the correct
operation of the TAM
circuit:
1. Check the signal
generated by the TAM: this
must be between 0-2 Vac.
2. Check the correct
connection between the
TAM and the board: restore
the connection if necessary.
3. Replace the TAM. 4.
Replace the board
3 fast flashes
Internal memory
error
The software or
the configuration
parameters are
corrupted.
Download the correct
configuration via humiSet;
replace the board.
-
yes
humidif.
stopped
4 fast flashes
Configuration
parameter error.
The configuration
parameters are
corrupted
-
yes
humidif.
stopped
5 fast flashes
Conductivity of the
water too high. The
alarm occurs:
• After 1 hour if
conductivity > b6
for more than 1
hour,
OR
• Immediately if
conductivity > 3x b6
High water
conductivity alarm
threshold.
Increase the high water
conductivity alarm
threshold with parameter
“b6”.
AUTO
yes
signal
only
humidif.
stopped
Conductivity of the
water higher than
1250 μS/cm.
Treat the supply water
with RO and ensure the
minimum supply water
requirements (see the KUE
manual) .
The water conductivity
must be between 75 and
1250 μS/cm. Softening
the water may worsen the
problem.
Conductivity
probes short-
circuited.
Clean the probes
Malfunction in the
conductivity meter
electrical circuit
a. Check the correct
operation of the
conductivity meter
electrical circuit:
1. Check the electrical
connections between the
conductivity meter and
the board: if necessary,
restore the connection.
2. Replace the conductivity
meter/fill tank.
3. Replace the board.
4. Replace the board..
Red LED on
board (if terminal
not connected)
(*)
description
cause
solution
reset
(press)
alarm relay
activation
action
6 fast flashes
memory backup
fails
internal memory
error
if the problem persists,
contact the CAREL service
center
--
no
signal
only
7 fast flashes
Maintenance time
expired. This is
displayed when:
hour counter >
bb (default 3000
hours).
Maintenance time
expired.
Replace /clean the
cylinder, then set the hour
counter to zero via RS485.
ESC
no
signal
only
8 fast flashes
Life timer expired.
This is displayed
when the hour
counter> 1.5xbb
(default 1.5x3000 =
4500 h)
Life timer expired.
Replace /clean the
cylinder, then set the hour
counter to zero.
counter
reste
yes
humidif.
stopped
Summary of Contents for IW Series
Page 1: ......
Page 2: ...76 5276 05 Page 2 of 82 ...
Page 4: ...76 5276 05 Page 4 of 82 ...
Page 6: ...76 5276 05 Page 6 of 82 ...
Page 11: ...76 5276 05 Page 11 of 82 Different air flow configuration ...
Page 12: ...76 5276 05 Page 12 of 82 IW 005 006 Side Air Flow Rear Air Return Indoor Unit Dimensions ...
Page 13: ...76 5276 05 Page 13 of 82 IW 005 006 Front Air Flow Rear Air Return Indoor Unit Dimensions ...
Page 14: ...76 5276 05 Page 14 of 82 IW 005 Outdoor Unit Dimensions ...
Page 15: ...76 5276 05 Page 15 of 82 IW 006 Outdoor Unit Dimensions ...
Page 24: ...76 5276 05 Page 24 of 82 Slideable Electrical Panel View ...
Page 27: ...76 5276 05 Page 27 of 82 Installation and Assembly ...
Page 60: ...76 5276 05 Page 60 of 82 Settings for Gmail ...
Page 61: ...76 5276 05 Page 61 of 82 ...
Page 69: ...76 5276 05 Page 69 of 82 ...
Page 73: ...76 5276 05 Page 73 of 82 Drain Pump Optional ...
Page 75: ...76 5276 05 Page 75 of 82 PLC Electrical connection diagram with remote display ...
Page 76: ...76 5276 05 Page 76 of 82 IW 005 006 Control Electrical Diagram ...
Page 77: ...76 5276 05 Page 77 of 82 IW 005 Power Electrical Diagram ...
Page 78: ...76 5276 05 Page 78 of 82 IW 006 Power Electrical Diagram ...
Page 82: ...76 5276 05 Page 82 of 82 ...