76-5276-05
Page 71 of 82
2 slow flashes
serial disconnected
Cable broken /
disconnected / not
properly connected
after the previous
set.
check the connection
of electricity and their
supervisor
AUTO
si
humidif.
stopped
if
enabling
(see “I”
62)
3 slow flashes
No supply water:
the humidifier tries
to add water but
the level inside
the cylinder does
not increase at the
expected speed
(the level of water
is estimated by
the TAM electrical
circuit).
Low supply water
pressure.
The water supply pressure
must be between 0.1 and
0.8 MPa (1-8 bars).
automatic
(after 10
minute
delay)
yes
(in 10
minute
delay )
humidif.
stopped
only
for 10
minutes
Steam hose bent,
choked or blocked
by condensate: this
may cause high
backpressure that
prevents the water
from being filled
into the cylinder
Check and reposition/
replace
Excessive
backpressure in the
hoses
To check this, switch the
unit off, remove the steam
hose from the cylinder
and switch the unit on:
fill water into the cylinder,
then reconnect the steam
hose.
Internal fill hoses
bent, choked or
blocked
Check and reposition /
clean/replace
The drain valve
leaks
Check and clean
Fill valve blocked or
malfunctioning.
Check the correct
operation of the fill valve:
1. Switch the unit off and
on again: can the noise
of the valve opening be
heard? YES: go to “2”; NO:
go to “3”.
2. Clean/replace. If the
internal flow limiter,
installed at the valve
outlet, is detached from
the valve, the water may
flow directly to the drain
through the fill tank as
the flow-rate is too high.
If this is the case, replace
the valve.
3. Replace the board.
Red LED on
board (if terminal
not connected)
(*)
description
cause
solution
reset
(press)
alarm relay
activation
action
4 slow flashes
Low steam flow-rate
during reduced
production. The
steam flow-rate is
estimated by the
TAM circuit
Conductivity of
the mains water
too low.
The water conductivity
must be between 75
and1250 μS/cm.
ESC
yes
humidif.
stopped
Too much foam in
the cylinder.
Perform the pre-wash (see
“Advanced functions”)
Excess scale in the
cylinder.
Clean/replace the cylinder.
TAM electrical
circuit not config.
correctly.
See solution to EF (relating to
TAM electrical circuit
not configured)
Malfunction in
the TAM electrical
circuit.
5 slow flashes
Drain problem
Check the drain pump and
fill connection
ESC
yes
humidif.
stopped
Check that the drain valve
is working correctly:
1. Switch unit off;
2. short-circuit M2.5 with
M2.6;
3. switch unit on;
4. can noise of the drain
valve opening be heard?
YES: remove drain valve
and clean; NO: replace
the valve.
Manifold blocked
Remove cylinder and valve
and clean manifold.
Cylinder filter
blocked
Replace the cylinder.
6 slow flashes
The cylinder requires
maintenance due to
the accumulation
of lime scale. The
“Cylinder almost
depleted” and
“Cylinder depleted”
warnings can be
disabled by b1-
parameter
The lime scale
limits steam
production.
Routine maintenance:
check the correct
operation of the cylinder,
clean it and, if necessary,
replace it.
ESC
no
signal
only
Summary of Contents for IW Series
Page 1: ......
Page 2: ...76 5276 05 Page 2 of 82 ...
Page 4: ...76 5276 05 Page 4 of 82 ...
Page 6: ...76 5276 05 Page 6 of 82 ...
Page 11: ...76 5276 05 Page 11 of 82 Different air flow configuration ...
Page 12: ...76 5276 05 Page 12 of 82 IW 005 006 Side Air Flow Rear Air Return Indoor Unit Dimensions ...
Page 13: ...76 5276 05 Page 13 of 82 IW 005 006 Front Air Flow Rear Air Return Indoor Unit Dimensions ...
Page 14: ...76 5276 05 Page 14 of 82 IW 005 Outdoor Unit Dimensions ...
Page 15: ...76 5276 05 Page 15 of 82 IW 006 Outdoor Unit Dimensions ...
Page 24: ...76 5276 05 Page 24 of 82 Slideable Electrical Panel View ...
Page 27: ...76 5276 05 Page 27 of 82 Installation and Assembly ...
Page 60: ...76 5276 05 Page 60 of 82 Settings for Gmail ...
Page 61: ...76 5276 05 Page 61 of 82 ...
Page 69: ...76 5276 05 Page 69 of 82 ...
Page 73: ...76 5276 05 Page 73 of 82 Drain Pump Optional ...
Page 75: ...76 5276 05 Page 75 of 82 PLC Electrical connection diagram with remote display ...
Page 76: ...76 5276 05 Page 76 of 82 IW 005 006 Control Electrical Diagram ...
Page 77: ...76 5276 05 Page 77 of 82 IW 005 Power Electrical Diagram ...
Page 78: ...76 5276 05 Page 78 of 82 IW 006 Power Electrical Diagram ...
Page 82: ...76 5276 05 Page 82 of 82 ...