3.2.1 Table mounted eye showers:
Install using the table mounting accessories M28x80mm. A hole of 30 mm diameter should
be made in the table top at a suitable point.
The table mounting accessories will be mounted with the plastic rosette and the counter nut
below the table surface.
3.2.2 Wall mounted eye showers:
Install using the wall flange. The wall flange should be installed with a suitable fastening
system on a flat surface (wall).
Installing using the male thread: Remove the bottom of the eye shower. Drill the embossed
holes and arrange the eye shower and mark the mounting holes.
3.2.3 Wall-/table mounted hand-held eye showers:
Install using the combined wall and table bracket. When using the combined bracket as a
wall bracket, the brass pipe must be unscrewed by hand - ensure that work gloves are worn
for this. The wall bracket should be mounted on an even surface (wall) using a suitable
fixing system. To achieve a wall spacing of 150 mm according to DIN EN 15154-2:2006, an
additional spacer (article number: BR 710 255) is available as an accessory. When using as a
table bracket, refer to the points under 4.2.1.
3.2.4 Wall mounted hand-held eye showers, 45° wall mounted:
Install using the 45° wall bracket. The wall bracket should be mounted on an even surface
(wall) using a suitable fixing system.
3.2.5 25°-table mounted hand-held eye shower:
Install using the 25° table mounting accessories M28x80mm. A hole of 30 mm diameter
should be made in the table top at a suitable point. The table mounting accessories will be
mounted with the plastic rosette and the counter nut below the table surface.
3.3 Position of strainer and gasket (Hand-held eye showers)
The strainer must be mounted between the eye shower and the hose; the gasket must be
mounted between the water inlet and the hose.
4. Water supply
The FAR eye shower should be connected to drinking water. The drinking water system
should be constructed in accordance with DIN 1988 and DIN EN 1717.
CAUTION! For new installations the water supply system must be rinsed out before
connecting the shower in order to prevent dirt damaging the valve.
4.1 Water supply for hand-held eye showers
The FAR hand-held eye shower is connected to the water supply using the ½ inch connection
nut on the hose. The FAR hand-held eye showers are fitted with a backflow preventer
according to DIN 1988 protection class 2 (3 for short periods). In addition, a second backflow
preventer can be obtained from specialized traders to achieve a higher protection class.
10
PRODUCT MANUAL
1800 358 101
www.westlab.com.au
09 972 7682
www.westlab.co.nz
646 568 5391
www.westlab.com
1 877 822 1455
www.westlab.com
Australia
New Zealand
United States