background image

Instructions for 

Digitrip RMS 500 Trip Unit 

Table  of  Contents 

1 .0 

General  Description . . . . . . . . . . . . . . . . . . . . . . . . .  . 

1 . 1 

Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

1 .2 

Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

1 .3 

Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

2.0 

U L  Listed  Devices . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

3.0 

Principle of Operation . . . . . . . . . . . . . . . . . . . . . . .  . 

3.1 

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

3.2 

Trip and Operation  Indicators . . . . . . . . . . . . . . . .  . 

3.3 

Test  Provisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

3.4 

Making  Current Release (Discrim inator) . . . . . .  . 

3.5 

I nstantaneous Override  . . . . . . . . . . . . . . . . . . . . .  . 

3.6 

Zone  I nterlocking . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

4.0 

Protection Settings . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

4 . 1  

General  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

4.2 

Long  Delay Settings  . . . . . . . . . . . . . . . . . . . . . . . .  . 

4.3 

Long  Delay Time Settings . . . . . . . . . . . . . . . . . . .  . 

4.4 

Short Delay Pick-up Settings  . . . . . . . . . . . . . . . .  . 

4.5 

Short Delay Time Settings  . . . . . . . . . . . . . . . . . .  . 

4.6 

I nstantaneous Pick-u p  Settings  . . . . . . . . . . . . . .  . 

4.7 

G round  Fault Cu rrent Pick-u p  Settings  . . . . . . .  . 

4.8 

G round  Fault Time Delay Settings  . . . . . . . . . . .  . 

5.0 

I nteg ral Test  Panel - Test  Procedu re  . . . . . . . . .  . 

5.1 

General  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

5.2 

When To Test  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

5.3 

Test  Provision  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

5.4 

Mode of Conducting Tests  . . . . . . . . . . . . . . . . . .  . 

5.4. 1 

Control  Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

5.4.2 

By  Not Tripping the Breaker . . . . . . . . . . . . . . . . .  . 

5.4.3 

By Tripping the B reaker . . . . . . . . . . . . . . . . . . . . .  . 

6.0 

Back-up Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

6. 1 

General  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

6.2 

Battery Check  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

6.3 

Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . .  . 

7.0 

Auxi liary Power Module . . . . . . . . . . . . . . . . . . . . .  . 

8.0 

Rati ng  Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

9.0 

References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

9.1 

Type  OS  Low Voltage AC Power Circuit 

Breakers  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

9.2 

Type  SPB Systems  Pow-R Breakers . . . . . . . . . .  . 

9.3 

Digitrip  RMS Trip Assembl ies  . . . . . . . . . . . . . . .  . 

9.4 

Series C® R-Frame  Molded Case Circuit 

Breakers  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

WARNING 

DO NOT ATTEMPT TO I N STALL OR PERFORM MAIN­

TENANCE ON EQUIPMENT WHILE IT IS ENERG IZED. 

DEATH OR SEVERE PERSONAL INJ URY CAN RESULT 
FROM  CONTACT  WITH  E N E RGIZED  EQUIPME NT. 

ALWAYS  VERIFY  THAT  NO  VOLTAG E  IS  PRESENT 

B E F O R E   P R O C E E D I N G   W I T H   THE  TAS K ,   A N D  

ALWAYS  FOLLOW G E N ERALLY ACCEPTED SAFETY 
PROCE D U R E S .   THE  WESTI N G H O U S E   ELECTR I C  
CORPORATION  IS NOT LIABLE  FOR THE  MISAPPLI­
CATION OR MISINSTALLATION OF ITS  PRODUCTS. 

Page 


























1 0  
1 0  
1 0  
1 0  
1 0  
1 0  
1 1  

1 1  
1 1  
1 1  

11 

The  user  is  cautioned to observe a l l  recommendations, warn­

ings and cautions relating to the safety of personnel and equip­

ment.  as well as  all  general and local health and safety  laws, 

codes,  and  procedures. 

The  recommendations  and  information  contained  herein  a re 
based on Westinghouse experience and judg ement, but should 

Effective May, 1 989 Supersedes I . L.  29-851  dated  March,  1 988 

I.L.  29-851 -A 

not  be considered to  be  al l-inclusive or covering every appli­

cation o r  circumstance which may arise. If any questions arise, 
contact  Westi nghouse  Electric  Corporation  for further  i nfor­
mation  or  i n structions. 

1 .0  General  Description 

1 . 1   Protection 

The  Digitrip R M S  500 Trip U nit, illustrated i n  Fig. 1 ,  is a m icro­

processor based type trip su itable for use in type SPB Systems 
Pow-R circuit  breakers and types DS and  DSL low voltage AC 
power  circuit  breakers  and  Series  C®  R-Frame  molded  case 
circuit  breakers. 

The  trip  unit  provides  true  RMS  current  sensing  for  proper 
correlation  with  thermal  characteristics  of  conductors  and 
equipment. I nterchangea ble rating plugs are provided to estab­

lish the continuous current rating  of each circuit breaker. 

The  Digitrip  RMS  500  Trip  Unit  is  completely  self-contai ned 
and  when  the  circuit  breaker  is  closed,  requ i res  no  external 
control  power to  operate  its 

protection  systems. 

It  operates 

from cu rrent signal  level s  and  control  power derived through 
current sensors i ntegrally mounted  in the circuit  breaker. 

The  Digitrip RMS 500 Trip  Unit is available in six optional pro­

tection  models.  Each trip  unit  may  be equ ipped with a  maxi­

mum of five phase and two g round (time-current) adjustments 

to  meet  specific  appl ication  requi rements.  These  protection 

models  i nclude the  fol lowing  types  which  a re  further  illus­

trated in the nameplate examples shown  in  Fig.  2. 

Figure 

Type  Protection 

2.1 

Long Time/Instantaneous 

2.2 

Long Time/Short Time 

2.3 

Long Ti me/Short Time/I nstantaneous 

2.4 

Long Time/I nstantaneous/Ground 

2.5 

Long Time/Short Time/G round 

2.6 

Long Time/Short Time/Instantaneous/ 
G round 

1 .2  Information 

Identifier 

(LI) 
(LS) 
(LSI) 
( LIG ) 
(LSG) 
(LSIG) 

Red LED indicators are provided on the face of the trip unit 

to indicate the mode of a n  automatic trip operation. A  bat­

tery  is  provided to maintain the  mode  of trip  LED  indication 

fol lowi ng  an automatic trip operation. 

G reen  LEOs are provided to indicate the  operational status of 

the trip unit and the status of the  back-up battery mou nted  i n  
the  rating p l u g .  

1 .3  Testing 

An  i ntegra l test panel, i ncluding a test selector switch and test 
and  reset  pushbuttons,  is  provided to  test the  circuit  breaker 

i n   either  a  "Trip"  or  "No-Trip"  test  mode  under  qualified 
conditions. 

2.0  UL  Li�ted  Devices 

Digitrip  RMS  500  Trip  U n its  are  l i sted  by  the  Underwriters 

Laboratories,  Inc.  for  use  in  types  SPB,  DS  and  DSL  and 

Series C  R-Frame ci rcuit breakers under U L  File  E781 9. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for Digitrip RMS 500

Page 1: ...act Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 5 00Trip Unit illustrated in Fig 1 is a micro processor based typ...

Page 2: ...ade m U S A VJ N Lithium Battery Only Long Delay Long Delay Setting Time In IT Sec At 61n 0 0 Breaker Trips In 6 T Test Amps IIJ in 0 Test 0 b Trip o IT In Reset 0 t n us lnst NP156P656H01 Fig 2 1 Lon...

Page 3: ...P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse Digital Protection D1g1tr1p RMS 500 CeliNa ___ 1NP256P655HOI Made 1n U S A II N L1th1um Battery Only Long Delay LongDelay Set...

Page 4: ...e pre set protection function pick up settings and other operating data stored in the ROM or Read Only Memory The microcomputer software program is then used in decision tree fashion to initiate prote...

Page 5: ...with an adjustable instantaneous setting i e types LS or LSG a high set non adjustable instantaneous override trip circuit is provided This high level tripping action is pre set to a specific value t...

Page 6: ...er in which the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit bre...

Page 7: ...me _____ I I I I I r Q Sec S 1 1 I I I u M I 1 1 I I I _ j 1 1 f l I I _ Available Settings 0 1 0 2 0 3 0 4 0 5 Seconds with Flat Response I I I m 1 j 1 1 I I w 3 0 1 0 3 0 5 Seconds with l t Response...

Page 8: ...t all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating In Any attempt to conduct in service testing above this value will b...

Page 9: ...g 6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fault condition occur during an in service No Trip Test sequence the protection functio...

Page 10: ...INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliary...

Page 11: ...ype SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master...

Page 12: ...Westinghouse Electric Corporation Distribution and Control Busi ness Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Page 13: ...ntact Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 500 Trip Unit illustrated in Fig 1 is a micro processor based t...

Page 14: ...0 l Cell No NP156P655H01 Made tn U S A y N Lith1um Battery Only Long Delay Long Delay Setting Time QJ In IT sec At 61n 0 0 Breaker Trips In 6T Test Amps ill In 0 Test 0 Trip 0 I In Reset 0 us lnst NP1...

Page 15: ...Amps 0 In 0 Test 0 Tnp 0 Reset Unit Status NP156P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse D1g1tal Protection Digitnp RMS 500 Cell No Gnd Fault Pickup In 0 long Delay...

Page 16: ...dly compared with the pre set protection function pick up settings and other operating data stored in the ROM or Read Only Memory The microcomputer software program is then used in decision tree fashi...

Page 17: ...not equipped with an adjustable instantaneous setting i e types LS or LSG a high set non adjustable instantaneous override trip circuit is provided This high level tripping action is pre set to a spec...

Page 18: ...the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit breaker Spe ci...

Page 19: ...I I Short Delay Time I 1 I I I Sec 0 1 1 I I I u I 1 1 I I I 1 1 1 In Viewing Window Indicates l t Type Response I I l J I I w Fig 4 4 Short Delay Time Settings r 1 I I I I lnst I I In i_ J 0 Availabl...

Page 20: ...e trip unit all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating In Any attempt to conduct in service testing above this va...

Page 21: ...Fig 6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fault condition occur during an in service No Trip Test sequence the protection func...

Page 22: ...O INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliar...

Page 23: ...pe SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master C...

Page 24: ...2 Westinghouse Electric Corporation Distribution and Control Business Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Page 25: ...ntact Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 500 Trip Unit illustrated in Fig 1 is a micro processor based t...

Page 26: ...No I NP256P655H01 Made in U S A lj3 N Lithium Battery Only Long Delay Long Delay Setting T1me ITJ in I Sec At 61n 0 0 Breaker Trips In 6T Test Amps In 0 Test 0 0 Trtp 0 I In Reset 0 us lnst NP256P656H...

Page 27: ...lay Time 0 Sec 0 b Ovemde D1scnmlnator Test 0 Trip o Reset NP256P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse D1gital Protection Digitnp RMS 500 Cell No r NP256P655H01 Mad...

Page 28: ...hich the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit breaker Sp...

Page 29: ...I I I I I Sec 0 I I I I I u _ M I I t 1 I I I 1 t 1 I I Available Settings 0 1 0 2 0 3 0 4 0 5 Seconds with Flat Response r j I I ill 1 J 1 1 I I w 3 0 1 0 3 0 5 Seconds with l t Response l t Respons...

Page 30: ...unit all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating Onl Any attempt to conduct in service testing above this value wi...

Page 31: ...6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fau lt condition occur during an in service No Trip Test sequence the protection function...

Page 32: ...O INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliar...

Page 33: ...pe SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master C...

Page 34: ...2 Westinghouse Electric Corporation Distribution and Control Business Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...